| Plan Review Notes For Permit 00111365 |
| Permit Number |
00111365 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-06-10 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT 1.2, MEN'S LOCKER RM, ENTERANCE | | | DOOR,SWINGS INTO STALL DOOR,SEC 4.22 | | | (2) SHT 3.4, DETAIL 9,12 RE: GRAB BAR | | | LENGTH,CONFLICTS WITH DETAIL ON SHT 3.8 | | | COMPLY W/FACBC 97 FIG.30 PG.108 | | | (3) SHT P-1, WATER SERVICE, BACK FLOW | | | PREVENTER REQ.SPC 94 SEC 606. | | | (4) SHT P-5 DOMESTIC WATER RISER,PIPE | | | SIZES, NO MORE THAN 2 FIXTURES ON 1/2" | | | COLD WATER, NO MORE THAN 4 FIXTURES ON | | | 1/2' HOT WATER.SPC 94 CNTY. W/AMENDMENTS | | | (5) SHT P-5, PLUMBING SPECIFICATIONS | | | MATRIALS, NOTE (F) AIR CHAMBERS TO BE | | | RECHARGEABLE & ACCESSIBLE. | | | SPC 94 SEC 607.8.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|