| Plan Review Notes For Permit 00111341 |
| Permit Number |
00111341 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM. MAIN | | | SHOWS 2P250A FEEDING PANEL INSIDE WITH | | | 1/0 CONDUCTORS. PLEASE ADJUST TO NEC. | | | | | | 2)NOTE: PLEASE NOTE AS PER 309.1 A WP | | | GFI RECEPT IS REQ`D FOR A/C COND UNITS. | | | | | | 3)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN DISC TO | | | PANEL. SIZE PER 250-122 | | | | | | 4)NOTE: PLEASE SEE PLANS. PLANS DON'T | | | SHOW MAIN NEXT TO METERCAN?? PLEASE | | | SHOW LOCATION ON PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|