2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM. MAIN
 SHOWS 2P250A FEEDING PANEL INSIDE WITH
 1/0 CONDUCTORS. PLEASE ADJUST TO NEC.
  
 2)NOTE: PLEASE NOTE AS PER 309.1 A WP
 GFI RECEPT IS REQ`D FOR A/C COND UNITS.
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL. SIZE PER 250-122
  
 4)NOTE: PLEASE SEE PLANS. PLANS DON'T
 SHOW MAIN NEXT TO METERCAN?? PLEASE
 SHOW LOCATION ON PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  