| Plan Review Notes For Permit 00111341 |
| Permit Number |
00111341 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | *************BUILDING UNSAT************* | | | | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVALS | | | FOR ALL EXTERIOR SWING DOORS TO BE USED | | | WITH APPROVED DRAWINGS. | | | | | | 2)PROVIDE SAFETY GLASS AS REQ PER 1997 | | | SBC 2405.2.1 (3) | | | | | | 3)PROVIDE TRUSS ENGINEERING SHEETS WITH | | | LAYOUT PLAN APPROVED BY DESIGNER OF | | | RECORD. | | | | | | 4)PROVIDE ENGINEERING FOR ALL BUTT GLASS | | | OPENINGS. | | | | | | 5)PROVIDE DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE. | | | | | | 6)NOTES ON SHEET A-1 REFERENCE ASCE 7-93 | | | (NOT CURRENT) AND UPLIFT CALCULATIONS | | | REFERENCES SBC SEC. 1606.2., MIXING | | | PROVISIONS FROM ASCE 7 AND 1606.2 SHALL | | | NOT BE PERMITTED 1997 SBC 1606.1.2.1. | | | | | | 7)PROVIDE DESIGN PRESSURES ON PLANS FOR | | | ALL EXTERIOR OPENINGS. | | | | | | ANY QUESTIONS,PLEASE CALL | | | FRANK KNAPP | | | BUILDING PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8392 |
|