Plan Review Notes
Plan Review Notes For Permit 00111288
Permit Number 00111288
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE HYDRANT LOCATIONS NOT SHOWN IN
 RELATIONSHIP TO FIRE DEPARTMENT
 CONNECTION. A FIRE HYDRANT IS TO BE NO
 FARTHER THAN 150 FEET FROM THE
 DEPARTMENT CONNECTION.
 2) NO CUT SHEETS PROVIDED ON FIRE
 SPRINKLER HEADS OR PIPING PLANNED FOR
 USE.
 3) PROVIDE MORE DETAILS ON FIRE HOSE
 CABINETS LOCATED IN WAREHOUSE AREA.
 4) ENTIRE BUILDING TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL MECHANICAL, ELECTRICAL AND STORAGE
 ROOMS. ALL VERTICAL SHAFTS ARE ALSO
 REQUIRED TO BE FIRE SPRINKLER PROTECTED.
 5) PLEASE PROVIDE DETAILS ON STORAGE
 RACKS PLANNED FOR USE. WHAT MATERIALS
 ARE THEY MADE OF.
 6) PLEASE PROVIDE FIRE HYDRANT
 INFORMATION ON BUILDING KEY PLAN.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910
  
 CALLED WIGINTON FIRE SPRINKLER TO PICK
 UP PLANS ON 11-30-00