| 2001-01-08 00:00:00 | 1) FIRE HYDRANT LOCATIONS NOT SHOWN IN | | | RELATIONSHIP TO FIRE DEPARTMENT | | | CONNECTION. A FIRE HYDRANT IS TO BE NO | | | FARTHER THAN 150 FEET FROM THE | | | DEPARTMENT CONNECTION. | | | 2) NO CUT SHEETS PROVIDED ON FIRE | | | SPRINKLER HEADS OR PIPING PLANNED FOR | | | USE. | | | 3) PROVIDE MORE DETAILS ON FIRE HOSE | | | CABINETS LOCATED IN WAREHOUSE AREA. | | | 4) ENTIRE BUILDING TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL MECHANICAL, ELECTRICAL AND STORAGE | | | ROOMS. ALL VERTICAL SHAFTS ARE ALSO | | | REQUIRED TO BE FIRE SPRINKLER PROTECTED. | | | 5) PLEASE PROVIDE DETAILS ON STORAGE | | | RACKS PLANNED FOR USE. WHAT MATERIALS | | | ARE THEY MADE OF. | | | 6) PLEASE PROVIDE FIRE HYDRANT | | | INFORMATION ON BUILDING KEY PLAN. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 | | | | | | CALLED WIGINTON FIRE SPRINKLER TO PICK | | | UP PLANS ON 11-30-00 |
|