Plan Review Notes
Plan Review Notes For Permit 00111283
Permit Number 00111283
Review Stop E
Sequence Number 3
Notes
Date Text
2001-11-27 00:00:00******************* UNSAT **************
  
 PLEASE NOTE, AS PER CONVERSATION WITH
 THE COMPANIES ENGINEER. THE FOLLOWING
 ITMES ARE TO BE CORRECTED.
  
 1)NOTE: PLEASE NOTE THAT EXISTING HSA
 MAIN 1OF2 IS SHOWN AS 1000A`S.
 THIS IS 400A PER CONVERSATION.
 THIS IS SHOWN AT MORETHAN ONE LOCATION
 ON PLAN.
  
 2)NOTE: PLEASE ALSO NOTE THAT PLANS SHOW
 3-SETS OF 4" CONDUITS WITH 4-400MCM`S
 IN EACH. PLEASE CLARIFY FOR ONLY 400A
 SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372