| Plan Review Notes For Permit 00111239 |
| Permit Number |
00111239 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | | | | 1)NOTE: PLEASE LABEL PANELS AND ALL | | | RISER EQUIPMENT TO CLARIFY WHICH ONE IS | | | WHICH. THE RISER ON THE RIGHT DOES NOT | | | SHOW FEEDING A 100 A PANEL?? | | | | | | 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH PANEL | | | SCHEDULES. | | | | | | 3) NOTE: PLEASE SEE ELEC RISER#2 WIRE | | | FEEDING 100A PANEL #4?? PLEASE SEE 310- | | | -16 FOR CORRECT WIRE SIZE.(75) COLULMN. | | | ALSO PLEASE SEE 1-#4? | | | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULE, #14 | | | WIRE ON 20A BRKR. | | | | | | 5)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS | | | FOR SERVICE AND NEW WORK. | | | | | | 6)NOTE: PLEASE CLARIFY ON PLAN THAT ALL | | | KITCHEN ELECTRICAL WORK IS EITHER EXIST- | | | -ING OR NEW. | | | | | | 7)NOTE: PLEASE SHOW WHERE THE 100A PANEL | | | IS BEING FED? IS IT THE 200A PANEL ON | | | THE SAME WALL. THE PLAN NEEDS TO SHOW | | | THE SEPARATION OF CIRCUITS FROM EACH | | | TENANT SPACE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL OR SET UP A MEETING . | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 ETX 8372 |
|