2001-02-05 00:00:001) FIRE HYDRANTS ARE TO BE WET PRIOR
 TO, DURING, AND AFTER CONSTRUCTION. FIRE
 LINES AND HYDRANTS ARE TO BE APPROVED
 BY UTILITIES PRIOR TO ACTIVATING THEM.
 2) FIRE HYDRANTS ARE TO MEET CITY
 UTILITY AND FIRE RESCUE STANDARDS.
 3) UNDERGROUND FIRE LINES TO BE PRESSURE
 TESTED AT 200 PSI FOR TWO HOURS.
 4) WHILE THE BUILDING IS UNDER
 CONSTRUCTION, SUITABLE ACCESS ROADS ARE
 TO BE PROVIDED FOR FIRE AND PARAMEDICAL
 PURPOSES.
  