Plan Review Notes
Plan Review Notes For Permit 00111182
Permit Number 00111182
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE DEPARTMENT ACCESS IS TO BE AT
 LEAST 20 FEET IN CLEAR WIDTH AND BE
 ABLE TO SUPPORT FIRE AND PARAMEDICAL
 EQUIPMENT. SOME AREAS INDICATES 12 FEET
 IN CLEAR WIDTH THAT DOES NOT MEET
 MINIMUM CODE REQUIREMENTS.
 2) FIRE HYDRANTS AND UNDERGROUND
 UTILITIES TO COMPLY WITH NFPA 24.
 3) PLEASE SHOW ALL FIRE HYDRANT
 LOCATIONS ON EXECUTIVE CENTER DRIVE
 EXTENSION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910