| Plan Review Notes For Permit 00111182 |
| Permit Number |
00111182 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE DEPARTMENT ACCESS IS TO BE AT | | | LEAST 20 FEET IN CLEAR WIDTH AND BE | | | ABLE TO SUPPORT FIRE AND PARAMEDICAL | | | EQUIPMENT. SOME AREAS INDICATES 12 FEET | | | IN CLEAR WIDTH THAT DOES NOT MEET | | | MINIMUM CODE REQUIREMENTS. | | | 2) FIRE HYDRANTS AND UNDERGROUND | | | UTILITIES TO COMPLY WITH NFPA 24. | | | 3) PLEASE SHOW ALL FIRE HYDRANT | | | LOCATIONS ON EXECUTIVE CENTER DRIVE | | | EXTENSION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|