| Plan Review Notes For Permit 00111172 |
| Permit Number |
00111172 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS PER | | | NFPA-72 2-2.1.1.1 | | | | | | 2)NOTE: PLEASE SEE THE AIC RATING FOR | | | BRKRS AT PANEL WERE SUBMITTED. THIS IS | | | CORRECT AND NEEDED BUT NO AIC RATING FOR | | | MAIN WAS SHOWN. PLEASE DO SO. PER 110-9 | | | | | | 3)NOTE: PLEASE CLARIFY ANY OF THE GFI | | | CIRCUITS SHOWN ON PANEL SCHEDULEFOR | | | BATH(S). PER 210-11-C-3 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESITONS | | | PLEASE CALL. | | | | | | DEWEWY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|