| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE; AS PER 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | SHOWN AS GFI/GFI PROTECTED. | | | | | | 2)NOTE: PLEASE SEE MISSING OUTLET PER | | | 210-52 FRONT BEDROOM. | | | | | | 3)NOTE:PLEASE NOTE THAT NO SWITCHES ORR | | | MEANS OF EGRESS LIGHTING IS SHOWN IN | | | MAIN/LIVING ROOM?? PER 210-70 | | | PLEASE SHOW | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|