| Plan Review Notes For Permit 00111091 |
| Permit Number |
00111091 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P-5 WATER HEATER DETAIL. WATER | | | HEATER CAN NOT INTERFERE WITH NORMAL | | | USE OF MOP SINK. | | | 2) SHT P-3 INTERGAL BACKFLOW PREVENTER | | | ARE NOT APPROVED. PLEASE PROVIDE BACK- | | | FLOW FOR ALL DENTAL EQUIPMENT AND PRO- | | | CESSOR. | | | 3) SHT'S P-1, P-2, & P-3, NO DETAIL FOR | | | WATER FEATURE SHOWN AS REQUESTED IN PRE- | | | VIOUS REVIEWS. | | | 4) SHT P-3, IF AIR CHAMBERS ARE TO BE | | | USED, SHOW DETAIL AS PER WH-PDI 201. | | | SEE ATTACHED SHEET FOR REFERENCE. | | | 5) SHT P-5, AS REQUESTED IN PREVIOUS RE- | | | VIEW, AIR GAP FOR PROCESSOR DRAIN NOT | | | APPROVED. PLEASE SEE ATTACHED SHEET FOR | | | APPROVED AIR GAP FITTING FOR THIS APPLI- | | | CATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|