Plan Review Notes
Plan Review Notes For Permit 00111091
Permit Number 00111091
Review Stop E
Sequence Number 5
Notes
Date Text
2002-06-11 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT "EQUIPMENT
 GROUNDING" CONDUCTORS ARE STILL BEING
 SHOWN BETWEEN METER AND GUTTER AND
 BETWEEN GUTTER AND MAIN DISC`S. THIS WAS
 REDLINED A YEAR AGO. PLEASE NOTE THAT
 THIS PARALELLING THE NEUTRAL. PLEASE SEE
 250-24
  
 2)NOTE: PLEASE NOTE THAT THERE ARE NO
 REVISIONS INDICATED BY EITHER CLOUDS OR
 TRIANLGES? NO DATES FO ANY REVISIONS
 ARE SHOWN IN THE UPPER RIGHT HAND CORNER
 ?? PLEASE SHOW BY CLOUDS OR TRIANGLES.
 NO INDICATIONS IF PLANS WERE COMPLETELY
 REDRAWN.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW, IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372