| Plan Review Notes For Permit 00111091 |
| Permit Number |
00111091 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-06-11 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT "EQUIPMENT | | | GROUNDING" CONDUCTORS ARE STILL BEING | | | SHOWN BETWEEN METER AND GUTTER AND | | | BETWEEN GUTTER AND MAIN DISC`S. THIS WAS | | | REDLINED A YEAR AGO. PLEASE NOTE THAT | | | THIS PARALELLING THE NEUTRAL. PLEASE SEE | | | 250-24 | | | | | | 2)NOTE: PLEASE NOTE THAT THERE ARE NO | | | REVISIONS INDICATED BY EITHER CLOUDS OR | | | TRIANLGES? NO DATES FO ANY REVISIONS | | | ARE SHOWN IN THE UPPER RIGHT HAND CORNER | | | ?? PLEASE SHOW BY CLOUDS OR TRIANGLES. | | | NO INDICATIONS IF PLANS WERE COMPLETELY | | | REDRAWN. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW, IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|