| Date |
Text |
| 2001-11-13 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) WATER HEATER TO HAVE PERMINATE SHIPS |
| | LADDER AND A WORKING PLATFORM MINIMUM |
| | DEMENSIONS 30"X30" TO MAKE WATER HEATER |
| | READILY ACCESSIBLE PER SPC SEC 501.7. |
| | 2) BACKFLOW REQUIRED FOR PROCESSOR |
| | 3) PAGE P1, PLEASE SUBMIT DETAILS FOR |
| | WATER FEATURE. AND SHOW HOW POTABLE |
| | WATER WILL BE PROTECTED. |
| | 4) PAGE P1, PAGE P5, VACUUMN DETAIL. VAC |
| | PUMP TO BE DIRECTLY CONNECTED TO SANT. |
| | SYSTEM. SEC 4-5.2.1.3 & 4-5.2.1.4 |
| | 5) PAGE P1, NO WATER SUPPLY SHOWN TO |
| | DRINKING FOUNTAIN. |
| | 6) PAGES P1, P3 & P5, WATER FILTER SHALL |
| | COMPLY WITH NSF STANDARDS. PLEASE SUBMIT |
| | MANUFACTURE INFORMATION TO SHOW FILTER |
| | COMPLIES WITH STANDARD. |
| | 7) PAGES P1 & P3, BACKFLOW REQUIRED ON |
| | WATER SERVICE AND ALL DENTAL EQUIPMENT. |
| | 8)PAGE P3, NOTES #1, & #2 TO READ SPC- |
| | 94 NOT SPC-97. |
| | 9)PAGE P3, AIR CHAMBERS ARE A "QUICK |
| | FIX" AND REQUIRE ACCESS PANELS. THEY |
| | ALSO SHALL BE RECHARGEABLE PER SPC-94 |
| | SEC 607.8.3. WATER HAMMER ARRESTORS |
| | SHOULD BE USED AND SIZED AND LOCATED PER |
| | MANUFACTURE INSTRUCTION AND PDI-WH 201, |
| | CLOSE TO FIXTURES NOT AT TOP OF DROP AS |
| | SHOWN ON RISER DIAGRAM. |
| | 10) PAGE P3, NO WATER SHOWN TO WATER |
| | FEATURE ON RISER DIAGRAM. |
| | 11) PAGE P5, AIR GAP FOR PROCESSOR DRAIN |
| | NOT APPROVED. PLEASE SEE ATTACHED SHEET |
| | FOR APPROVED AIR GAP FITTING FOR THIS |
| | APPLICATION. |
| | 12) PAGES P1 & P2, DRINKING FOUTAIN. |
| | PLEASE PROVIDE PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | SHOW HOW D.F. WILL COMPLY WITH FACBC SEC |
| | 4.15 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |