Plan Review Notes
Plan Review Notes For Permit 00111091
Permit Number 00111091
Review Stop P
Sequence Number 4
Notes
Date Text
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) WATER HEATER TO HAVE PERMINATE SHIPS
 LADDER AND A WORKING PLATFORM MINIMUM
 DEMENSIONS 30"X30" TO MAKE WATER HEATER
 READILY ACCESSIBLE PER SPC SEC 501.7.
 2) BACKFLOW REQUIRED FOR PROCESSOR
 3) PAGE P1, PLEASE SUBMIT DETAILS FOR
 WATER FEATURE. AND SHOW HOW POTABLE
 WATER WILL BE PROTECTED.
 4) PAGE P1, PAGE P5, VACUUMN DETAIL. VAC
 PUMP TO BE DIRECTLY CONNECTED TO SANT.
 SYSTEM. SEC 4-5.2.1.3 & 4-5.2.1.4
 5) PAGE P1, NO WATER SUPPLY SHOWN TO
 DRINKING FOUNTAIN.
 6) PAGES P1, P3 & P5, WATER FILTER SHALL
 COMPLY WITH NSF STANDARDS. PLEASE SUBMIT
 MANUFACTURE INFORMATION TO SHOW FILTER
 COMPLIES WITH STANDARD.
 7) PAGES P1 & P3, BACKFLOW REQUIRED ON
 WATER SERVICE AND ALL DENTAL EQUIPMENT.
 8)PAGE P3, NOTES #1, & #2 TO READ SPC-
 94 NOT SPC-97.
 9)PAGE P3, AIR CHAMBERS ARE A "QUICK
 FIX" AND REQUIRE ACCESS PANELS. THEY
 ALSO SHALL BE RECHARGEABLE PER SPC-94
 SEC 607.8.3. WATER HAMMER ARRESTORS
 SHOULD BE USED AND SIZED AND LOCATED PER
 MANUFACTURE INSTRUCTION AND PDI-WH 201,
 CLOSE TO FIXTURES NOT AT TOP OF DROP AS
 SHOWN ON RISER DIAGRAM.
 10) PAGE P3, NO WATER SHOWN TO WATER
 FEATURE ON RISER DIAGRAM.
 11) PAGE P5, AIR GAP FOR PROCESSOR DRAIN
 NOT APPROVED. PLEASE SEE ATTACHED SHEET
 FOR APPROVED AIR GAP FITTING FOR THIS
 APPLICATION.
 12) PAGES P1 & P2, DRINKING FOUTAIN.
 PLEASE PROVIDE PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 SHOW HOW D.F. WILL COMPLY WITH FACBC SEC
 4.15
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377