| Plan Review Notes For Permit 00111091 |
| Permit Number |
00111091 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-12-10 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | THE FOLLOWING COMMENT IS NUMBERED AS PER | | | THE 11/26/01 BUILDING PLAN REVIEW: | | | | | | 3) STRUCTURAL CALCULATIONS.COMMENT NOT | | | ADDRESSED.SUBMIT CALCULATIONS FOR THE | | | REVISED LOAD PATHS DUE TO THE ROOF | | | RE-CONFIGURATION AND REVISED COLUMN | | | ARRANGEMENT. | | | ---------------------------------------- | | | | | | PROVISO: | | | | | | WINDOW PRODUCT APPROVAL.THE LARGE | | | ARCHED WINDOW ON THE WEST ELEVATION OF | | | THE VESTIBULE IS LARGER THAN THE PRODUCT | | | APPROVAL DIMENSIONS FOR LARGE MISSILE | | | IMPACT WINDOWS (SEE PGT INDUSTRIES | | | DRAWING NO.4231, SHEET 3).EITHER | | | SHUTTERS MUST BE PROVIDED OR A RELEVANT | | | PRODUCT APPROVAL SUBMITTED. | | | | | | | | | END OF REVIEW COMMENTS | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|