Plan Review Notes For Permit 00111091
Permit Number 00111091
Review Stop B
Sequence Number 3
Notes
Date Text
2001-12-05 00:00:00ADDITIONAL NOTES
 NOTES ON SUBMITTALS SINCE PLAN REVIEW
 NUMBERED AS PER ORIGINAL COMMENTS:
  
 7) PRODUCT APPROVALS.THE SUBMITTED
 WINDOW/DOOR ASSEMBLY PRODUCT APPROVALS
 STATE THAT THEY ARE FOR "SINGLE UNIT
 APPLICATIONS ONLY".AS THEY DO NOT
 CORRELATE TO THE PROPOSED ARCHED
 WINDOWS, FURTHER PRODUCT APPROVALS ARE
 REQUIRED TO COVER THE GLAZED OVER-PANELS
 AND ASSOCIATED MULLIONS.
2001-11-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC* = STANDARD BUILDING CODE AMENDMENTS
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY = FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING COSTRUCTION
  
  
 1) CONFIRM THAT SITE PLAN IS UNCHANGED
 TO VERIFY ADEQUATE HORIZONTAL SEPARATION
  
 2) FL ENERGY 103.3 - SUBMIT ENERGY CODE
 COMPLIANCE CALCULATIONS.
  
 3) ROOF RE-CONFIGURED AND COLUMNS
 REVISED.SUBMIT STRUCTURAL
 CALCULATIONS FOR REVISED LOAD PATHS.
  
 4) COLUMN ON FOOTING F-3 IS SHOWN AS
 4"X4"X1/2" ON FOUNDATION PLAN,
 5"X5"X1/4" ON COLUMN SCHEDULE AND
 6"X6"X1/2" ON ROOF FRAMING PLAN.
 CLARIFICATION REQUIRED.
  
 5) FOUNDATION PLAN, SLAB SECTION A-A:
 EXPANSION JOINT REQUIRED.
  
 6) FL ACC CODE 4.13.6 - MINIMUM
 MANEUVERING CLEARANCES HAVE NOT
 BEEN PROVIDED AT THE DOORS TO MALE
 TOILET, FEMALE TOILET OR SUPPLY ROOM
 (ROOM 06). REVISION REQUIRED.
  
 7) WINDOWS HAVE BEEN CHANGED TO ARCHED
 WINDOWS.SUBMIT PRODUCT APPROVALS TO
 INCLUDE THE GLAZED OVER-PANELS AND
 ADDITIONAL MULLIONS
  
 8) SBC 2405.2 - THE GLAZING IN THE
 WINDOW ADJACENT THE EXIT DOOR FROM THE
 STAFF LOUNGE REQUIRES TEMPERED GLASS.
 SHUTTERS ARE REQUIRED FOR LARGE MISSILE
 IMPACT PROTECTION.