| 2001-12-05 00:00:00 | ADDITIONAL NOTES |
| | NOTES ON SUBMITTALS SINCE PLAN REVIEW |
| | NUMBERED AS PER ORIGINAL COMMENTS: |
| | |
| | 7) PRODUCT APPROVALS.THE SUBMITTED |
| | WINDOW/DOOR ASSEMBLY PRODUCT APPROVALS |
| | STATE THAT THEY ARE FOR "SINGLE UNIT |
| | APPLICATIONS ONLY".AS THEY DO NOT |
| | CORRELATE TO THE PROPOSED ARCHED |
| | WINDOWS, FURTHER PRODUCT APPROVALS ARE |
| | REQUIRED TO COVER THE GLAZED OVER-PANELS |
| | AND ASSOCIATED MULLIONS. |
| 2001-11-26 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC* = STANDARD BUILDING CODE AMENDMENTS |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | FL ENERGY = FLORIDA ENERGY EFFICIENCY |
| | CODE FOR BUILDING COSTRUCTION |
| | |
| | |
| | 1) CONFIRM THAT SITE PLAN IS UNCHANGED |
| | TO VERIFY ADEQUATE HORIZONTAL SEPARATION |
| | |
| | 2) FL ENERGY 103.3 - SUBMIT ENERGY CODE |
| | COMPLIANCE CALCULATIONS. |
| | |
| | 3) ROOF RE-CONFIGURED AND COLUMNS |
| | REVISED.SUBMIT STRUCTURAL |
| | CALCULATIONS FOR REVISED LOAD PATHS. |
| | |
| | 4) COLUMN ON FOOTING F-3 IS SHOWN AS |
| | 4"X4"X1/2" ON FOUNDATION PLAN, |
| | 5"X5"X1/4" ON COLUMN SCHEDULE AND |
| | 6"X6"X1/2" ON ROOF FRAMING PLAN. |
| | CLARIFICATION REQUIRED. |
| | |
| | 5) FOUNDATION PLAN, SLAB SECTION A-A: |
| | EXPANSION JOINT REQUIRED. |
| | |
| | 6) FL ACC CODE 4.13.6 - MINIMUM |
| | MANEUVERING CLEARANCES HAVE NOT |
| | BEEN PROVIDED AT THE DOORS TO MALE |
| | TOILET, FEMALE TOILET OR SUPPLY ROOM |
| | (ROOM 06). REVISION REQUIRED. |
| | |
| | 7) WINDOWS HAVE BEEN CHANGED TO ARCHED |
| | WINDOWS.SUBMIT PRODUCT APPROVALS TO |
| | INCLUDE THE GLAZED OVER-PANELS AND |
| | ADDITIONAL MULLIONS |
| | |
| | 8) SBC 2405.2 - THE GLAZING IN THE |
| | WINDOW ADJACENT THE EXIT DOOR FROM THE |
| | STAFF LOUNGE REQUIRES TEMPERED GLASS. |
| | SHUTTERS ARE REQUIRED FOR LARGE MISSILE |
| | IMPACT PROTECTION. |