Plan Review Notes
Plan Review Notes For Permit 00111091
Permit Number 00111091
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1.MOP SINK CLOSET TO HAVE EXHAUST FAN
 PER 1997 SMC 501.4
 2. DUCT DETECTOR TO BE TIED TO BLDG FIRE
 ALARM OR HORN AND STROBE FOR NOTIFICATIO
 PER 1996 NFPA 90A
 3. MEDICAL GAS SYSTEMS REQUIRE SEPARATE
 PERMIT. SUBMIT PLANS AT TIME OF MECHANI-
 CAL PERMIT APPLICATION FOR THIS WORK.