| Plan Review Notes For Permit 00111091 |
| Permit Number |
00111091 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM. AN | | | EQUIPMENT GROUNDING CONDUCTOR IS SHOWN | | | IN RISER AND FROM METERCAN TO FIRST | | | MEANS OF DISCONNECT. PLEASE NOTE PER 250 | | | OF THE NEC ONLY AFTER FIRST MEANS. | | | | | | 2)NOTE: PLEASE SEE E-4. THIS SHOWS AIC | | | RATINGS FOR ALL PANELS BUT NOTHING FOR | | | MAINS? PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT. PER 110-9 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|