Plan Review Notes
Plan Review Notes For Permit 00111091
Permit Number 00111091
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM. AN
 EQUIPMENT GROUNDING CONDUCTOR IS SHOWN
 IN RISER AND FROM METERCAN TO FIRST
 MEANS OF DISCONNECT. PLEASE NOTE PER 250
 OF THE NEC ONLY AFTER FIRST MEANS.
  
 2)NOTE: PLEASE SEE E-4. THIS SHOWS AIC
 RATINGS FOR ALL PANELS BUT NOTHING FOR
 MAINS? PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. PER 110-9
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372