Plan Review Notes
Plan Review Notes For Permit 00110906
Permit Number 00110906
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE SHOWN AS GFI/GFI
 PROTECTED PER 210-8-A-6
  
 2)NOTE: PLEASE SEE MISSING GFI FOR POWD-
 -ER ROOM. PER 210-52D AND 210-11-C3
  
 3)NOTE: PLEASE SEE MISSING OUTLETS PER
 210-52 FOR 2` OF WALL SPACE.
  
 4)NOTE: SMOKE DETECTOR REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS OF NEW CONST-
 -RUCTION. NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE NOTE AS PER 250-50 NEW
 BLDG STEEL AT NEW GARAGE TO BE BONDED.
 PLEASE SHOW WITH COLD WATER.
  
 6)NOTE: PLEASE NOTE THAT NOW A NEW SERV-
 -ICE IS BEING INSTALLED. PLEASE PROVIDE
 AIC RATINGS FOR ALL NEW EQUIPMENT BEING
 INSTALLED. MUST BE RATED FOR THE AVAIL-
 ABLE FAULT CURRENT PER 110-9.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372