| Plan Review Notes For Permit 00110906 |
| Permit Number |
00110906 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: ALL OUTLETS SERVING KITCHEN | | | COUNTERSPACE ARE TO BE SHOWN AS GFI/GFI | | | PROTECTED PER 210-8-A-6 | | | | | | 2)NOTE: PLEASE SEE MISSING GFI FOR POWD- | | | -ER ROOM. PER 210-52D AND 210-11-C3 | | | | | | 3)NOTE: PLEASE SEE MISSING OUTLETS PER | | | 210-52 FOR 2` OF WALL SPACE. | | | | | | 4)NOTE: SMOKE DETECTOR REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS OF NEW CONST- | | | -RUCTION. NFPA-72 2-2.1.1.1 | | | | | | 5)NOTE: PLEASE NOTE AS PER 250-50 NEW | | | BLDG STEEL AT NEW GARAGE TO BE BONDED. | | | PLEASE SHOW WITH COLD WATER. | | | | | | 6)NOTE: PLEASE NOTE THAT NOW A NEW SERV- | | | -ICE IS BEING INSTALLED. PLEASE PROVIDE | | | AIC RATINGS FOR ALL NEW EQUIPMENT BEING | | | INSTALLED. MUST BE RATED FOR THE AVAIL- | | | ABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|