| Plan Review Notes For Permit 00110799 |
| Permit Number |
00110799 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | | | | 1.PLUMBING RISER DIAGRAM NOT TO CODE. | | | SHOW PROPER VENTING. | | | | | | 2.IF ICE MACHINES DRAIN FLOOR DRAINS | | | MUST BE INSTALLED TO ALLOW I.M. TO | | | DRAIN INDURECTLY TO THE DRAINAGE | | | SYSTEM. | | | | | | 3.A-3 BEDROOM 2 SHOWER MUST BE AT LEAST | | | 30" WIDE AND HAVE 1024 SQ. IN. | | | INTERIOR ROOM. | | | | | | 4.BACKFLOW PREVENTOR MUST BE INSTALLED | | | IF ONE WATER METER IS USED FOR BOTH | | | DWELLINGS. SHOW WATER RISER. | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|