2001-01-08 00:00:00DENIED;
  
 1.IS WATER HEATER GAS OR ELECTRIC?
 ENERGY CAULKS CALL FOR ELECTRIC, PLANS
 SHOW GAS. IF GAS SHOW VENTING AND
 COMBUSTION AIR CALKULATIONS.
  
 2.M-1 IN LIBRARY A 12X12 DROP WITH 210
 CFM'S IS SHOWN, WHAT SIZE DUCT AND
 WHERE IS DUCT RUN FROM?
  
 3.M-1 SECOND FLOOR, LEFT SIDE OF A/H#1
 6" DUCT AND DROP HAVE NO SIZE OR CFM'S
  
 4.BATHROOM EXHAUST FANS MUST VENT TO
 OUTSIDE.
  
 5.ATTIC ACCESS MUST BE NO LESS THAN
 22X36 INCHES. THE ATTIC OPENING SHALL
 NOT BE MORE THAN 20 FEET FROM
 EQUIPMENT AND HAVE A PASSAGE WAY ALSO
 WORKING CLEARANCE MUST BE MET. PER
 97 SMC 304.4.1.
  
 6.GUEST HOUSE. A/C FOR FIRST FLOOR?
 NONE SHOWN.
  
 7.WHAT SIZE IS R/A DUCT SECOND FLOOR.
  
 8.WATER HEATER [SAME AS NOTE 1]
  
 9.ATTIC ACCESS [SAME AS NOTE 5]
  
 MECHANICAL PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377