| Plan Review Notes For Permit 00110799 |
| Permit Number |
00110799 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | | | | 1.IS WATER HEATER GAS OR ELECTRIC? | | | ENERGY CAULKS CALL FOR ELECTRIC, PLANS | | | SHOW GAS. IF GAS SHOW VENTING AND | | | COMBUSTION AIR CALKULATIONS. | | | | | | 2.M-1 IN LIBRARY A 12X12 DROP WITH 210 | | | CFM'S IS SHOWN, WHAT SIZE DUCT AND | | | WHERE IS DUCT RUN FROM? | | | | | | 3.M-1 SECOND FLOOR, LEFT SIDE OF A/H#1 | | | 6" DUCT AND DROP HAVE NO SIZE OR CFM'S | | | | | | 4.BATHROOM EXHAUST FANS MUST VENT TO | | | OUTSIDE. | | | | | | 5.ATTIC ACCESS MUST BE NO LESS THAN | | | 22X36 INCHES. THE ATTIC OPENING SHALL | | | NOT BE MORE THAN 20 FEET FROM | | | EQUIPMENT AND HAVE A PASSAGE WAY ALSO | | | WORKING CLEARANCE MUST BE MET. PER | | | 97 SMC 304.4.1. | | | | | | 6.GUEST HOUSE. A/C FOR FIRST FLOOR? | | | NONE SHOWN. | | | | | | 7.WHAT SIZE IS R/A DUCT SECOND FLOOR. | | | | | | 8.WATER HEATER [SAME AS NOTE 1] | | | | | | 9.ATTIC ACCESS [SAME AS NOTE 5] | | | | | | MECHANICAL PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|