| 2001-01-16 00:00:00 | PASSED WITH PROVISOS: |
| | THE DRIVEWAY CAN NOT BE INSTALLED WHERE |
| | SHOWN ON THE PLAN.THERE MUST BE FIVE |
| | FOOT OF CLEARANCE FROM THE EDGE OF THE |
| | DRIVE TO THE HYDRANT. IF THE DRIVEWAY |
| | HAS TO BE INSTALLED AT THIS LOCATION THE |
| | N THE PROPERTY OWNER MUST RELOCATED THE |
| | FIRE HYDRANT AT THEIR COST.THE NEW |
| | FIRE HYDRANT LOCATION MUST BE FIVE FOOT |
| | FROM THE NEW DRIVEWAY. THIS FIRE HYDRANT |
| | WAS INSTALLED IN JUNE OF 2000. |
| | SIDEWALK AND DRIVEWAY REQUIREMENTS: |
| | ALL BROKEN SIDEWALKS ALONG THE FRONT OF |
| | THE PROPERTY MUST BE REPLACED. |
| | ALL DRIVEWAY APPROACHES THAT ARE NOT TO |
| | BE USED MUST BE REMOVED AND REPLACED |
| | WITH NEW CURBS (AND GUTTERS). |
| | ALL DRIVEWAYS MUST BE TO THE ATTACHED |
| | CITY STANDARD DRIVEWAY INDEX. |
| | ALL GRADES FOR CITY SIDEWALKS AND DRIVES |
| | MUST BE SET UP BY THE CITY SURVEY CREW. |
| | CALL ED RYAN AT 659-8040 TO SET UP AN |
| | APPOINTMENT. |
| | ALL RIGHT OF WAY PERMIT MUST BE APPLIED |
| | FOR TO INSTALL THE DRIVEWAY APPROACH AND |
| | SIDEWALKS.APPLY FOR THE PERMIT AT THE |
| | ENGINEERING DEPARTMENT AT 1000-45TH ST. |
| | WATER AND SEWER: |
| | A RPZA BACKFLOW PREVENTER MUST BE |
| | INSTALLED AT THE PROPERTY LINE. |
| | A CLEAN-OUT IS REQUIRED ON THE SEWER |
| | LINE AT THE PROPERETY LINE. |
| | NO TREES CAN BE PLANTED WITHIN FIVE FOOT |
| | OF ANY WATER, SANITARY OR STORM LINE OR |
| | APPURTANANCES OWNED BY THE CITY.THIS |
| | INCLUDES HYDRANTS AND WATER SERVICES |
| | AND SANITARY SEWER LATERALS. |