| 2001-01-08 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT THE AVAILABLE |
| | FAULT IS SHOWN BUT PLEASE LIST THE RAT- |
| | -ING OF THE PANEL. ALSO PLEASE LIST THE |
| | AIC RATING OF MAIN DISCONNECT. PLEASE |
| | SUBMIT CLARIFICATIONOF RISER DIAGRAM |
| | AND PLANS. PLAN SHOWS MAIN DISCONNECT |
| | NEXT TO METER? AND RISER SHOWS PANEL |
| | BEING NEMA-1 INSIDE.??? PLEASE CORRELATE |
| | |
| | |
| | 2)NOTE: PLEASE SEE 210-52 FOR OUTLET |
| | SPACING REQ`MENTS. 2`,6` RULE. |
| | |
| | 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. PER 210-8-A-6. |
| | |
| | 4)NOTE: PLEASE SEE MECH CODE 300.9 FOR |
| | 'WP GFI REQ`D FOR A/C COND UNITS. |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210-11-C-3 AND |
| | 210-52D. MUST BE #12 AND 20A. |
| | |
| | 6)NOTE: PLEASE NOTE THAT THE GAS WATER |
| | HEATER MAY NOT BE PERMITTED IN UNDER |
| | SEC 504 OF THE GAS CODE, 504.1 |
| | |
| | 7)NOTE: PLEASE SEE THE REQ`MENTS FOR |
| | GARAGE OUTLET, 210-52G AND MUST BE GFI |
| | PER 210-8. |
| | |
| | 8)NOTE: PLEASE NOTE THAT THE SAME |
| | NOTE PERTAINS TO GARAGE FOR CLARIFICAT- |
| | -ION OF SERVICE/PANEL/DISCONNECT. |
| | AIC RATINGS ETC.215-5 |
| | |
| | 9)NOTE: SMOKE DETECTOR ON EACH LEVEL |
| | FOR APT. |
| | |
| | 10)NOTE: PLEASE NOTE BATH(S) CIRCUIT |
| | FOR APT ALSO. PER 210-11-C-3 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORAMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |