2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE AVAILABLE
 FAULT IS SHOWN BUT PLEASE LIST THE RAT-
 -ING OF THE PANEL. ALSO PLEASE LIST THE
 AIC RATING OF MAIN DISCONNECT. PLEASE
 SUBMIT CLARIFICATIONOF RISER DIAGRAM
 AND PLANS. PLAN SHOWS MAIN DISCONNECT
 NEXT TO METER? AND RISER SHOWS PANEL
 BEING NEMA-1 INSIDE.??? PLEASE CORRELATE
  
  
 2)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING REQ`MENTS. 2`,6` RULE.
  
 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210-8-A-6.
  
 4)NOTE: PLEASE SEE MECH CODE 300.9 FOR
 'WP GFI REQ`D FOR A/C COND UNITS.
  
 5)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3 AND
 210-52D. MUST BE #12 AND 20A.
  
 6)NOTE: PLEASE NOTE THAT THE GAS WATER
 HEATER MAY NOT BE PERMITTED IN UNDER
 SEC 504 OF THE GAS CODE, 504.1
  
 7)NOTE: PLEASE SEE THE REQ`MENTS FOR
 GARAGE OUTLET, 210-52G AND MUST BE GFI
 PER 210-8.
  
 8)NOTE: PLEASE NOTE THAT THE SAME
 NOTE PERTAINS TO GARAGE FOR CLARIFICAT-
 -ION OF SERVICE/PANEL/DISCONNECT.
 AIC RATINGS ETC.215-5
  
 9)NOTE: SMOKE DETECTOR ON EACH LEVEL
 FOR APT.
  
 10)NOTE: PLEASE NOTE BATH(S) CIRCUIT
 FOR APT ALSO. PER 210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  