Plan Review Notes
Plan Review Notes For Permit 00110788
Permit Number 00110788
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)RECORDED COPY OF NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITED TO CITY BUILDING DEPT. BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED.
  
 3)PROVIDE SPECIFIC DETAILS FOR INTERIOR
 AND EXTERIOR STAIRS INCLUDING DIMENSIONS
 FOR ALL COMPONENTS. 97 SBC 104.2
  
 4)PROVIDE FLOOR AND ROOF TRUSS PLANS
 INDICATING THE CALCULATED UPLIFTS AND
 THE SPECIFIC CONNECTORS TO BE USED.
  
 5)PROVIDE FOUNDATION PLAN INDICATING
 LOCATIONS OF PADS FOR STEEL COLUMNS,
 ADDED FOOTINGS AT FRONT PORCH,AT BEARING
 WALLS OF STAIRWELL,FOOTINGS FOR COVERED
 DECK. PROVIDE COLUMN SPACING,ETC.
  
 6)PROVIDE SPECIFIC DETAILS FOR GUARDRAIL
 AT COVERED DECK. SPECIFY MATERIAL,SPAC-
 ING OF INTERMEDIATE RAILS,SPACING OF
 SUPPORTS,METHOD OF ATTACHMENT,ETC.
  
 7)PROVIDE ATTIC VENTILATION.97SBC 2309.7
  
 8)PROVIDE CRAWL VENTILATION. SPECIFY
 SIZE,LOCATION AND NUMBER OF VENTS.97SBC
 1804.6.2 NOTE:ACCESS IS REQUIRED TO
 USABLE CRAWL SPACE.
  
 9)PROVIDE 2 COPIES OF FL ENERGY CODE
 COMPLIANCE FORMS AND MANUAL "J" CALCS.
  
 10)SAFETY GLASS IS REQUIRED IN BATHROOMS
 97SBC 2405.2
  
 11)PROVIDE FLOOR AND CEILING ELEVATIONS
 FROM FINISH GRADE. INDICATE MEAN ROOF
 HEIGHT.
  
 12)PROVIDE VIEWS OF ALL FOUR ELEVATIONS
 ON PLANS.
  
 13)PLANS APPEAR TO INDICATE RELOCATION
 OF EXISTING ENTRY DOOR ON 1ST FLOOR.
 PLANS DO NOT INDICATE PORCH OR STEPS AT
 RELOCATED DOOR. PLEASE CLARIFY.
  
 14)TRUSS LAYOUTS AND TRUSS DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD AND TO BE SO
 NOTED AND SIGNED BY THE DESIGNER OF THE
 STRUCTURE.NOTE: PLEASE CHECK THE DIMEN-
 SIONS,THE TRUSS LAYOUT AND AND PLANS DO
 NOT CONCUR.
  
 15)PROVIDE FASTENING DETAILS FOR ATTACH-
 ING THE 3 PLIES OF LVL TOGETHER.
  
 16)PROVIDE DETAILS ON LOAD BEARING WALLS
 AT STAIR OPENING SUPPORTING FLOOR TRUSS-
 ES F2 AND GIRDER TRUSS G2, INCLUDING
 FOUNDATION.
  
 17)PROVIDE 2 COPIES OF KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
 ALSO PROVIDE AN ADDITIONAL COPY OF THE
 PRODUCT APPROVAL, ONLY 1 COPY WAS
 RECIEVED.
  
 18)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR ROOF COVERING. THE ONES
 SUBMITTED HAD EXPIRED PRIOR TO APPLICAT-
 ION DATE.
  
 19)PRODUCT APPROVALS FOR FRENCH DOORS
 WERE SUBMITTED.PLEASE INDICATE WHERE
 THEY WILL BE LOCATED ON THE PLANS.
  
 20)PROVIDE PRODUCT APPROVALS FOR SLIDING
 GLASS DOORS SHOWN ON PLANS.