2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS OF NEW AND ON EACH LEVEL.ALSO
 FOR EXISTING BEDROOM(S) PER NFPA-72 2-2.
 .1.1.1.
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 REQ`D BY 220-3-C-1
 PLEASE SHOW EXISTING SERVICE SIZE/FEEDER
 -S,/ PANEL SCHEDULES,,,,,, 215-5
  
 3)NOTE: A/C LOADS??
  
 4)NOTE: PLEASE SHOW ANY CATV AND TELE-
 -PHONES AND LOCATIONS ON PLANS.
  
 5)NOTE: PLEASE SHOW OUTLETS IN BATHS AS
 GFI REQ`D PER 210-8.
  
 6)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3
  
 7)NOTE: PLEASE SEE CLOSET CLEARENCES PER
 410-8. PLEASE SHOW TYPE OF FIXTURE.
  
 8)NOTE: PLEASE SEE 210-52E FOR WP GFI
 OUTLET FRONT OF DWELLING.
  
 9)NOTE: PLAN SHOWS MORE THAN 50% OF THE
 WIRING IN HOUSE AS BEING NEW. ALL ELEC-
 -TRICAL IN HOUSE MAY NEED TO BE BROUGHT
 UP TO CODE AS REQ`D AND SUBJECT TO
 ELECTRICAL INSPECTION.
  
 10NOTE: PLEASE SHOW OUTLET ON BACK PORCH
 AS GFI PER 210-8
  
  
 PLEASE SUBMIT AND SHOW ALL OF THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372