| 2001-01-08 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| | ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- |
| | -ING ROOMS OF NEW AND ON EACH LEVEL.ALSO |
| | FOR EXISTING BEDROOM(S) PER NFPA-72 2-2. |
| | .1.1.1. |
| | |
| | 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | REQ`D BY 220-3-C-1 |
| | PLEASE SHOW EXISTING SERVICE SIZE/FEEDER |
| | -S,/ PANEL SCHEDULES,,,,,, 215-5 |
| | |
| | 3)NOTE: A/C LOADS?? |
| | |
| | 4)NOTE: PLEASE SHOW ANY CATV AND TELE- |
| | -PHONES AND LOCATIONS ON PLANS. |
| | |
| | 5)NOTE: PLEASE SHOW OUTLETS IN BATHS AS |
| | GFI REQ`D PER 210-8. |
| | |
| | 6)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3 |
| | |
| | 7)NOTE: PLEASE SEE CLOSET CLEARENCES PER |
| | 410-8. PLEASE SHOW TYPE OF FIXTURE. |
| | |
| | 8)NOTE: PLEASE SEE 210-52E FOR WP GFI |
| | OUTLET FRONT OF DWELLING. |
| | |
| | 9)NOTE: PLAN SHOWS MORE THAN 50% OF THE |
| | WIRING IN HOUSE AS BEING NEW. ALL ELEC- |
| | -TRICAL IN HOUSE MAY NEED TO BE BROUGHT |
| | UP TO CODE AS REQ`D AND SUBJECT TO |
| | ELECTRICAL INSPECTION. |
| | |
| | 10NOTE: PLEASE SHOW OUTLET ON BACK PORCH |
| | AS GFI PER 210-8 |
| | |
| | |
| | PLEASE SUBMIT AND SHOW ALL OF THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |