| 2002-01-22 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 2) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | FRONT MISSING |
| | |
| | 3) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | SHOWN ON ONE PANEL, BUT NOT THE OTHER? |
| | |
| | 5)NOTE: PLEASE NOTE MISSING HALL OUTLET |
| | PER 210-52 H |
| | |
| | 6)NOTE: PLEASE NOTE CLEARENCE FOR AHU |
| | DISC, FIRST FLOOR 110-26. ORIG PLANS |
| | SHOW DISC IN UNIT? |
| | |
| | 7)NOTE: PLEASE NOTE MISSING FOOTER STEEL |
| | PER 250-50 AND ON ORIG PLANS? |
| | |
| | 8)NOTE: PLEASE NOTE PANELS ARE SHOWN |
| | AT 150A AND PANEL SCHEDULES ARE SHOWN AT |
| | 300AMPS?? |
| | |
| | 9)NOTE: PLEASE NOTE POOL HEATER SHOWN ON |
| | PANEL SCHEDULES BUT NOT, IN LOAD CALCS?? |
| | |
| | 10)NOTE: PLEASE NNOTE TWO 3000W WATER |
| | HEATERS SHOWN ON SCHEDULES, BUT ONLY |
| | ONE 4500W ON LOAD CALCS??? |
| | |
| | 11)NOTE: PLEASE NOTE, PLANS ARE STILL |
| | SHOWING EXISTING HOUSE GL? PLEASE NOTE |
| | THIS IS NOT REALLY EXSITING SINCE THE |
| | ENTIRE STRUCTURE IS RE-DONE? |
| | PLEASE CLARIFY PLANS SHOW NEW FRONT |
| | HOUSE SERVICE? AND WHAT ABOUT SERIVCE TO |
| | ANY OTHER HOUSE? IS THERE ARE "BACK" |
| | HOUSE? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THEREARE ANYQUESTIONS, |
| | PLEASE CALL. |
| | |