| Date |
Text |
| 2001-07-17 00:00:00 | 1-FRENCH DOORS PRODUCT APPROVAL THAT WAS |
| | SUBMITTED IS GOOD ONLY FOR DOUBLE |
| | DOORS AS SHOWN ON APPROVED DRAWINGS. |
| | -NEED TO PROVIDE PRODUCT APPROVAL FOR |
| | FRENCH DOORS WITH SIDELITES SINGLE |
| | ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS |
| | 2-PROVIDE PRODUCT APPROVAL FOR: |
| | -FIXED WINDOWS. |
| | -ROUND WINDOWS. |
| | -EXTERIOR SWING SINGLE DOORS. |
| | -ENTRY DOOR WITH SIDELITES AND TRANSOM |
| | ABOVE AS SHOWN ON ARCHITECT'S PLANS. |
| | 3-TRUSS DRAWINGS: |
| | A)TRUSS ENGINEER TO PROVIDE ALL HIS INFO |
| | ON TRUSS LAYOUT AS REQUIRED BY CHAPTER |
| | 471 OF FLORIDA STATUTES. |
| | B)TRUSS ENGINEER TO HAVE ORIGINAL |
| | SIGNATURE ON ALL ENGINEERED TRUSSES AS |
| | REQUIRED BY CHAPTER 471 FL. STATUTES. |
| | C)TRUSS ENGINEER TO UPDATE ALL GENERAL |
| | TRUSS DETAILS. USE ASCE 7-95 (NOT 93) |
| | FOR 145MPH. |
| | ALSO, PROVIDE ORIGINAL SIGNATURE AND |
| | DATE OF SEALING THE DRAWING. CH. 471. |
| | D)ENGINEERED TRUSSES TO BE REVISED USING |
| | ASCE 7-95 FOR 145MPH (NOT 140MPH). |
| | E)TRUSS LAYOUT AND ARCHITECT'S ROOF |
| | FRAMING PLAN ARE DIFFERENT. ROOF TRUSS |
| | LAYOUT CALLS FOR A 4" COL. TO SUPPORT |
| | TRUSS MG16. REVISE PLANS SHOWING THE |
| | RIGHT COLUMN SIZE AND CONNECTIONS AT |
| | SECOND FLOOR AND ROOF AREA. |
| | -ALSO, PROVIDE COLUMN DETAIL SHOWING |
| | SUPPORT OF TRUSS FG-7 AND FG-9. |
| | F)CONNECTOR SPECIFIED FOR TRUSS HG-13 |
| | DOESN'T RESIST THE LOADS CALCULATED ON |
| | THE ENGINEERED TRUSSES. REVISE AS |
| | REQUIRED. |