| 2001-01-08 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE NOTES ON ME-1. THE |
| | TOP OF THE NOTES SAY ALL NOTES BELOW |
| | PERTAIN TO THIS PLAN. PLEASE SEE NOTES,, |
| | CASH REGISTER? FUSED MAIN DISCONNECTS?? |
| | PLEASE CLARIFY. |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULES AND |
| | RISER,,, RISER SHOWS 150A MAINS AND |
| | PANEL SCH SHOWS 300A MAINS??? PLEASE |
| | CORRELATE. |
| | |
| | 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR |
| | ALL MAINS AND BREAKERS. ALL MAINS/PANELS |
| | MUST BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110-9 |
| | |
| | 4)NOTE: PLEASE SEE LOAD CALCULATIONS,,, |
| | WHIRLPOOL IN MB SHOWN?? PLEASE SEE |
| | PANEL SCHED.?? AND PLAN DOES NOT SHOW |
| | IN MASTER BATH. |
| | |
| | 5)NOTE: PLEASE SEE LOAD CALCS. WATER |
| | HEATER SHOWN AT 4500W`S. THIS ALSO DOES- |
| | -NOT CORRELATE WITH PANEL SCHEDULES. |
| | PANELS SHOW MORE THAN ONE WATER HEATER?? |
| | ALSO THE LOAD FOR WATER HEATERS FOR BOTH |
| | NEED TO CORRELATE W/ LOAD CALCS. |
| | |
| | 6)NOTE: POOL HEATER SHOWN ON PANEL SCHED |
| | -ULE BUT NOT SHOWN ON LOAD CALCS. ????? |
| | PLEASE DO SO. |
| | |
| | 7)NOTE: PLEASE CLARIFY THE MAIN?METER |
| | COMBO. ALSO PLEASE SHOW ALL EQUIPMENT |
| | AND SHOW LOCATIONS OF ALL EQUIPMENT ON |
| | PLANS/PANELS/METER ETC. |
| | |
| | THE FOLLOWING IS FOR E-1.0 |
| | |
| | 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| | ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- |
| | -ING ROOMS AND ON EACH LEVEL OF DWELLING |
| | PER NFPA-72 2-2.1.1.1 PLEASE SHOW ALL |
| | REQ`D. |
| | |
| | 2)NOTE: PLEASE SEE MISSING GFI OUTLETS |
| | PER 210-52E FRONT AND REAR OF DWELLING. |
| | |
| | 3)NOTE: PLEASE SEE MISSING OUTLETS FOR |
| | HALLWAY(S) PER 210-52H |
| | |
| | 4)NOTE: PLEASE SEE MISSING OUTLETS SPAC- |
| | -ING PER 210-52 |
| | |
| | 5)NOTE: PLEASE SEE LOCATIONS SHOWN FOR |
| | DISCONNECTS THROUGHOUT HOUSE. MUST MEET |
| | 110-26 FOR CLEARENCE REQ`MENTS. |
| | |
| | 6)NOTE: PLEASE SEE MISSING OUTLETS PER |
| | MECH CODE FOR CONDENSING UNITS. WP GFI`S |
| | 309-1. |
| | |
| | THE FOLLOWING IS FOR SECOND FLOOR E-2.0 |
| | |
| | MOST OF THE SAME NOTES FROM FIRST FLOOR |
| | FOR SD`S, OUTLET SPACING AND DISCONNECT |
| | CLEARENCE. |
| | |
| | |
| | PLEASE SHOW AND SUBMIT ALL THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT 8372 |