| 2001-01-08 00:00:00 | ********PLEASE REVISE ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT PLANS WITH MORE |
| | ELECTRICAL DETAIL SHOWN. |
| | |
| | 2)NOTE: PLEASE SHOW A/C UNITS. SHOW |
| | DISCONNECTS PER 440-11 AND RECEPT PER |
| | LOCAL MECH CODE. |
| | |
| | 3)NOTE: NO HWH SHOWN?? IS THIS CORRECT? |
| | IF THERE IS ONE PLEASE SHOW ON PANEL |
| | AND PLAN. INCLUDE ON LOAD CALCS. |
| | |
| | 4)NOTE: PLEASE NOTE THAT SD`S ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | PER NFPA-72 2-2.1.1.1 |
| | |
| | 5)NOTE: PLEASE LABEL/SHOW ALL OUTLETS |
| | THAT MEET THE REQ`MENTS FOR 210-8 AS |
| | GFI/GFI PROTECTED. |
| | |
| | 6)NOTE:PLEASE INCLUDE BLDG STEEL AND CWP |
| | AS PART OF THE GROUNDING BOND AT CABANA. |
| | PER 250-50 |
| | |
| | 7)NOTE: PLEASE NOTE THAT IF THERE IS |
| | GOING TO BE ANY LOW VOLTAGE IN THE |
| | CABANA THEN PLEASE SHOW ON PLAN. THIS |
| | MIGHT INCLUDE CATV,TELEPHONE,SPEAKERS |
| | ETC. PLEASE NOTE SEPARATE LV PERMIT |
| | IS REQ`D OR INCLUDE ON THIS PERMIT. |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | NEW EQUIPMENT BEING INSTALLED. MAINS |
| | /PANELS MUST BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. PER 110-9 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW BEFORE ROUGH INSPECTION. |
| | IF THERE ANY QUESTIONS PLEASE CALL. |
| | |