Plan Review Notes
Plan Review Notes For Permit 00110647
Permit Number 00110647
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00********PLEASE REVISE **************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH MORE
 ELECTRICAL DETAIL SHOWN.
  
 2)NOTE: PLEASE SHOW A/C UNITS. SHOW
 DISCONNECTS PER 440-11 AND RECEPT PER
 LOCAL MECH CODE.
  
 3)NOTE: NO HWH SHOWN?? IS THIS CORRECT?
 IF THERE IS ONE PLEASE SHOW ON PANEL
 AND PLAN. INCLUDE ON LOAD CALCS.
  
 4)NOTE: PLEASE NOTE THAT SD`S ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 PER NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE LABEL/SHOW ALL OUTLETS
 THAT MEET THE REQ`MENTS FOR 210-8 AS
 GFI/GFI PROTECTED.
  
 6)NOTE:PLEASE INCLUDE BLDG STEEL AND CWP
 AS PART OF THE GROUNDING BOND AT CABANA.
 PER 250-50
  
 7)NOTE: PLEASE NOTE THAT IF THERE IS
 GOING TO BE ANY LOW VOLTAGE IN THE
 CABANA THEN PLEASE SHOW ON PLAN. THIS
 MIGHT INCLUDE CATV,TELEPHONE,SPEAKERS
 ETC. PLEASE NOTE SEPARATE LV PERMIT
 IS REQ`D OR INCLUDE ON THIS PERMIT.
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED. MAINS
 /PANELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT. PER 110-9
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ROUGH INSPECTION.
 IF THERE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372