| Plan Review Notes For Permit 00110627 |
| Permit Number |
00110627 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | AND SIZE OF EXISTING SERVICE. PER | | | 220-3-C-1 | | | | | | | | | 2)NOTE: PLEASE SHOW RISER DIAGRAM WITH | | | NEW EQUIPMENT BEING INSTALLED. PLEASE | | | SHOW ALL GROUNDING FOR NEW EQUIPMENT AND | | | BONDING OF NEW BLDG STEEL. PER 250-50 | | | | | | 3)NOTE: PLEASE SUBMIT PANEL SHEDULES FOR | | | NEW PANEL SHOWN. PLEASE INCLUDE THE | | | REQ`D BATH(S) CIRCUIT(S) PER 210-11-C-3 | | | MUST BE #12 AND 20A. | | | | | | 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS OR ROOMS | | | THAT CAN BE CONVERTED TO SLEEPING ROOMS. | | | THESE ROOMS ARE ANY ROMMS WITH ADJACENT | | | CLOSETS OR BATHROOMS. THE ABOVE IS PER | | | NFPA-72 2-2.1.1.1 | | | | | | 5)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | OUTSIDE AREAS AS GFI/GFI PROTECTED. | | | PER 210-8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|