Plan Review Notes
Plan Review Notes For Permit 00110627
Permit Number 00110627
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 AND SIZE OF EXISTING SERVICE. PER
 220-3-C-1
  
  
 2)NOTE: PLEASE SHOW RISER DIAGRAM WITH
 NEW EQUIPMENT BEING INSTALLED. PLEASE
 SHOW ALL GROUNDING FOR NEW EQUIPMENT AND
 BONDING OF NEW BLDG STEEL. PER 250-50
  
 3)NOTE: PLEASE SUBMIT PANEL SHEDULES FOR
 NEW PANEL SHOWN. PLEASE INCLUDE THE
 REQ`D BATH(S) CIRCUIT(S) PER 210-11-C-3
 MUST BE #12 AND 20A.
  
 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OR ROOMS
 THAT CAN BE CONVERTED TO SLEEPING ROOMS.
 THESE ROOMS ARE ANY ROMMS WITH ADJACENT
 CLOSETS OR BATHROOMS. THE ABOVE IS PER
 NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 OUTSIDE AREAS AS GFI/GFI PROTECTED.
 PER 210-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372