2001-01-08 00:00:00PLUMBING PLAN REVIEWDENIED
 (1)SHT 3/3 SPC 94 SEC 407.2.2 DRINKING
 FOUNTAIN REQ.TO BE H/C AND ACCESSIBLE TO
 THE PUBLIC.FACBC 4.1.3 (10)(A)
 FOR PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
 (2) SHT 3/3 AIR CHAMBERS TO BE
 ACCESSIBLE & RECHARGEABLE,SPC 94
 SEC 607.8.3
 END OF COMMENTSPAUL SCHMITZ