Plan Review Notes
Plan Review Notes For Permit 00110544
Permit Number 00110544
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE THE REQ`MENTS OF THE
 F.A.C SEC. 553-79-6A. PLANS ARE TO SIGN-
 -ED AND SEALED BY AN P.E. UNDER 471.025
  
 2)NOTE" PLEASE SUBMIT AND SHOW AIC RAT-
 -INGS FOR ALL NEW EQUIPMENT AND BRKRS
 BEING INSTALLED. ALL MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
  
 3)NOTE: PLEASE NOTE THAT A MAIN DISC/
 MCB IS REQ`D ON THE LOAD SIDE OF THE
 TANSFORMER.
  
 4)NOTE: PLEASE PROVIDE MORE DETAIL FOR
 WIRES/CONDUIT SIZES FROM DISC TO TRANS.
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% AND ALL TRACK LIGHTING PER NEC
 ART; 220-12B
  
 6)NOTE:PLEASE SHOW TRANSFORMER SIZE??
  
 7)NOTE: PLEASE SHOW GROUNDING FOR THE
 TRANSFORMER FOR SEP DERIVED SYSTEM.
  
 8)NOTE: PLEASE SHOW LOCATIONS FOR ALL
 EQUIPMENT BEING INSTALLED. PER 215-5
  
 9)NOTE:PLEASE SHOW ON PLAN THE COLOR
 CODING FOR WIRING PER LOCAL CODE/AMEND.
  
 PLEASE SUBMIT ALL THE ABOVE INFOMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELETRICALPLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT8372