| 2001-02-12 00:00:00 | 2/12/01 GENERAL CONT. DELETE PLUMB TO | | | COME IN WITH SEPERATE PLANS PERMIT & | | | FEES. 02/12/01 JW | | 2001-02-11 00:00:00 | PLUMBING PLAN REVIEW 2ND TIME DENIED | | | REFERENCES STD PLBG CODE 94 | | | RE: COMMENTS FROM KAMM CONSULTING INC | | | DATED 01-17-01 | | | (1)SHT.P0.1 WTR HTR DETAIL CONFLICTS | | | WITH NOTE # 1, COMMENTS.T/P,P/D TO BE | | | READLY OBSERVIBLE. SEC 507.8.4 PAN DRAIN | | | 1", T/P 3/4" ALL INDIRECT WASTE TO FLOOR | | | SINKS, THIS LOCATION IS NOT READLY | | | OBSERVIBLE SEC 507.8.4 | | | (2) WATER HEATER IN CORNER KITCHEN | | | CABNET IS NOT READLY ACCESSIBLE.SEC501.7 | | | T/P,PAN DRAIN,SHALL BE READLY OBSERVED, | | | SEC 507.8.4 | | | (3)SHT.P-5.1DWV ISOMETRIC,IS NOT | | | COMPLETE, SHOW ENTIRE SYSTEM SEC 104.3 | | | (4) SHT P2.2 NEW COMMENT SEC 409.4.5 | | | ROOMS CONTANING LAUNDARY MACHINES SHALL | | | BE PROVIDED WITH A FLOOR DRAIN. | | | END OF COMMENTS QUESTIONS PAUL SCHMITZ | | | 561-659-8096 |
|