2001-02-08 00:00:00PROVISO:
 PRIOR COMMENTS ACCEPTED BY REVISION AND
 COMMENTS DATED 2/8/01 BY THIS OFFICE
 WITH THE PROVISO THAT THE DRYER EXHAUST
 DUCT PENETRATING RATED WALLS SHALL
 COMPLY WITH ALL 4 PARTS OF 610.1.3.
 26 GA. METAL
 5 FOOT RUN ON BOTH SIDES OF THE RATED
 WALL BEFORE ANY OPENING
 UNDER 100 SQ. IN.
 AND THE DUCT SHALL BE ABOVE A CEILING