| 2001-01-26 00:00:00 | 1) CODE ANALYSIS BOX INCORRECT. TRAVEL |
| | DISTANCE FOR EXISTING APARTMENTS AND |
| | MERCANTILE OCCUPANCIES WHEN SPRINKLERED |
| | IS 150 FEET. |
| | 2) PROVIDE COMPLETE FIRE ALARM SYSTEM |
| | SHOP DRAWINGS. CUT SHEETS, |
| | WIRING DIAGRAM AND BATTERY CALCULATIONS |
| | ARE TO BE PROVIDED. THE FIRE ALARM NOTES |
| | SECTION INDICATES CLASS B, STYLE C |
| | CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS |
| | OR FULLY ADDRESSABLE WILL BE PERMITTED. |
| | ALSO DUCT SMOKE DETECTORS MUST ACTIVATE |
| | THE FIRE ALARM SYSTEM AND NOT JUST |
| | A SUPERVISORY SIGNAL. SEPARATE PLANS |
| | AND PERMITS REQUIRED. |
| | 3) EXIT DOORS CANNOT SWING ONTO |
| | SIDEWALKS. EXIT DOORS MUST BE RECESSED. |
| | 4) FIRE SEPARATIONS BETWEEN MERCANTILE |
| | AND RESIDENTIAL OCCUPANCIES TO COMPLY |
| | WITH BUILDING CODE REGULATIONS. |
| | 5) THE FIRE SPRINKLER DRAWINGS THAT |
| | WERE ATTACHED MUST BE SUBMITTED UNDER |
| | A SEPARATE PERMIT TO THE CONSTRUCTION |
| | SERVICES DEPARTMENT. THE FIRE DEPARTMENT |
| | CONNECTION MUST BE LOCATED NO FARTHER |
| | THAN 150 FEET FROM A FIRE HYDRANT. |
| | 6) ALL EXITS TO COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 101, THE LIFE |
| | SAFETY CODE, 1985 EDITION. |
| | |