Plan Review Notes
Plan Review Notes For Permit 00110504
Permit Number 00110504
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-26 00:00:001) CODE ANALYSIS BOX INCORRECT. TRAVEL
 DISTANCE FOR EXISTING APARTMENTS AND
 MERCANTILE OCCUPANCIES WHEN SPRINKLERED
 IS 150 FEET.
 2) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS. CUT SHEETS,
 WIRING DIAGRAM AND BATTERY CALCULATIONS
 ARE TO BE PROVIDED. THE FIRE ALARM NOTES
 SECTION INDICATES CLASS B, STYLE C
 CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS
 OR FULLY ADDRESSABLE WILL BE PERMITTED.
 ALSO DUCT SMOKE DETECTORS MUST ACTIVATE
 THE FIRE ALARM SYSTEM AND NOT JUST
 A SUPERVISORY SIGNAL. SEPARATE PLANS
 AND PERMITS REQUIRED.
 3) EXIT DOORS CANNOT SWING ONTO
 SIDEWALKS. EXIT DOORS MUST BE RECESSED.
 4) FIRE SEPARATIONS BETWEEN MERCANTILE
 AND RESIDENTIAL OCCUPANCIES TO COMPLY
 WITH BUILDING CODE REGULATIONS.
 5) THE FIRE SPRINKLER DRAWINGS THAT
 WERE ATTACHED MUST BE SUBMITTED UNDER
 A SEPARATE PERMIT TO THE CONSTRUCTION
 SERVICES DEPARTMENT. THE FIRE DEPARTMENT
 CONNECTION MUST BE LOCATED NO FARTHER
 THAN 150 FEET FROM A FIRE HYDRANT.
 6) ALL EXITS TO COMPLY WITH THE
 REQUIREMENTS OF NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION.
  