| Plan Review Notes For Permit 00110504 |
| Permit Number |
00110504 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.WATER HEATER PAN DRAINS AND RELIOF | | | LINES MUST RUN TO THE OUTSIDE. 94 SPC. | | | 507.8.4 AND 807.3. | | | | | | 2.WATER HEATERS MUST BE READILY ACCESS- | | | IBLE. CABINET MUST HAVE A DOOR THAT | | | OPENS WITHOUT USING TOOLS AND OPENING | | | MUST BE LARGER THAN WATER HEATER. | | | PLEASE SHOW DETAIL. | | | | | | 3.P6.1,EACH APARTMENT MUST HAVE AN | | | ACCESSIBLE SHUTOFF VALVE AHEAD OF THE | | | FIRST BRANCH CONNECTION. 610.1. | | | | | | 4.SHUTOFF VALVES REQUIRED FOR LAUNDRY | | | FACILITIES. | | | | | | 5.SHOW SHUTOFF VALVES AT THE BASE OF | | | EACH RISER ON WATER RISER DIAGRAM AS | | | SHOWN ON PAGE P3.1. | | | | | | 6.SANITARY RISER DIAGRAM REQUIRED. | | | PAGE P5.1 NOT WITH PLANS. | | | | | | 7.PAGE P0.1 NOTE #10 WATER DISTRIBUTION | | | PIPING BELOW GROUND MUST BE MINIMUM | | | "L" COPPER PIPE. CITY AMENDMENTS 611.3 | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|