Plan Review Notes
Plan Review Notes For Permit 00110504
Permit Number 00110504
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001.WATER HEATER PAN DRAINS AND RELIOF
 LINES MUST RUN TO THE OUTSIDE. 94 SPC.
 507.8.4 AND 807.3.
  
 2.WATER HEATERS MUST BE READILY ACCESS-
 IBLE. CABINET MUST HAVE A DOOR THAT
 OPENS WITHOUT USING TOOLS AND OPENING
 MUST BE LARGER THAN WATER HEATER.
 PLEASE SHOW DETAIL.
  
 3.P6.1,EACH APARTMENT MUST HAVE AN
 ACCESSIBLE SHUTOFF VALVE AHEAD OF THE
 FIRST BRANCH CONNECTION. 610.1.
  
 4.SHUTOFF VALVES REQUIRED FOR LAUNDRY
 FACILITIES.
  
 5.SHOW SHUTOFF VALVES AT THE BASE OF
 EACH RISER ON WATER RISER DIAGRAM AS
 SHOWN ON PAGE P3.1.
  
 6.SANITARY RISER DIAGRAM REQUIRED.
 PAGE P5.1 NOT WITH PLANS.
  
 7.PAGE P0.1 NOTE #10 WATER DISTRIBUTION
 PIPING BELOW GROUND MUST BE MINIMUM
 "L" COPPER PIPE. CITY AMENDMENTS 611.3
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377