2001-01-08 00:00:00****************DENIED******************
 1.EXHAUST DUCT PENETRATING RATED WALLS
 TO HAVE FIRE DAMPERS PER 610.1.2 OR
 COMPLY WITH ALL 4 PARTS OF 610.1.3 (3)
 EXCEPTIONS.
 2. DRYER VENTS DO NOT COMPLY WITH 1997
 SMC 613.4 OR 509.
 EACH DRYER VENT DUCT SHALL BE RUN TO
 THE OUTSIDE OF THE BUILDING IN A DIRECT
 AS POSSIBLE MANNER.
 FIRE DAMPERS SHALL BE SPECIFICALLY
 LISTED FOR USE IN THE DRYER EXHAUST
 SYSTEM.
 DETAILS ON CONNECTION OF TWO OR MORE
 DRYER VENTS NEED TO BE PROVIDED FOR
 REVIEW.
 ACCESS FOR CLEANING THE ENTIRE DUCT
 SYSTEM SHALL BE PROVIDED. SHOW DETAILS
 ON PLANS.
 NO DUCTS ARE SHOWN FOR THE THIRD
 FLOOR LAUNDRY.
 MULTIPLE FAMILY USE OF THIS EQUIPMENT
 REQUIRES COMMERCIAL DESIGN OF THE DUCT
 SYSTEM. SHOW DUCT TYPE AND CLEARANCE
 FROM COMBUSTIBLE DETAIL SHOWING COMPLI-
 ANCE WITH 1997 SMC 509.4.
 3. PROVIDE OUTSIDE AIR CALCULATIONS
 SHOWING COMPLIANCE W/ ASHRAE 62-89.