| Plan Review Notes For Permit 00110504 |
| Permit Number |
00110504 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1.EXHAUST DUCT PENETRATING RATED WALLS | | | TO HAVE FIRE DAMPERS PER 610.1.2 OR | | | COMPLY WITH ALL 4 PARTS OF 610.1.3 (3) | | | EXCEPTIONS. | | | 2. DRYER VENTS DO NOT COMPLY WITH 1997 | | | SMC 613.4 OR 509. | | | EACH DRYER VENT DUCT SHALL BE RUN TO | | | THE OUTSIDE OF THE BUILDING IN A DIRECT | | | AS POSSIBLE MANNER. | | | FIRE DAMPERS SHALL BE SPECIFICALLY | | | LISTED FOR USE IN THE DRYER EXHAUST | | | SYSTEM. | | | DETAILS ON CONNECTION OF TWO OR MORE | | | DRYER VENTS NEED TO BE PROVIDED FOR | | | REVIEW. | | | ACCESS FOR CLEANING THE ENTIRE DUCT | | | SYSTEM SHALL BE PROVIDED. SHOW DETAILS | | | ON PLANS. | | | NO DUCTS ARE SHOWN FOR THE THIRD | | | FLOOR LAUNDRY. | | | MULTIPLE FAMILY USE OF THIS EQUIPMENT | | | REQUIRES COMMERCIAL DESIGN OF THE DUCT | | | SYSTEM. SHOW DUCT TYPE AND CLEARANCE | | | FROM COMBUSTIBLE DETAIL SHOWING COMPLI- | | | ANCE WITH 1997 SMC 509.4. | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS | | | SHOWING COMPLIANCE W/ ASHRAE 62-89. |
|