Plan Review Notes
Plan Review Notes For Permit 00110504
Permit Number 00110504
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 BE INSTALLED ON BUILDING AND COMPLY WITH
 CITY CODE REQUIREMENTS.
 2) DOOR SWING IMPROPER ON MERCANTILE
 SPACE THAT DISPLAYS A 77 FOOT MAXIMUM
 TRAVEL DISTANCE. THE OCCUPANT LOAD
 IS MORE THAN 50, SO EXIT DOORS SHALL
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 3) FIRE SPRINKLER SYSTEM, FIRE
 RESCUE CONNECTION SHOWN ON SPRINKLER
 DRAWINGS TO BE NO MORE THAN 150 FEET
 FROM A FIRE HYDRANT. ENTIRE BUILDING TO
 BE COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL ELECTRICAL, MECHANICAL
 AND SERVICE ROOMS. ALSO VERTICAL SHAFTS.
 4) ELEVATION DRAWINGS DO NOT INCLUDE
 HEIGHTS.
 5) FUTURE TENANT SPACES TO BE AT LEAST
 ONE HOUR FIRE SEPARATED FROM ONE
 ANOTHER.
 6) DOORS TO APARTMENTS TO BE AT LEAST
 20 MINUTE FIRE DOORS EQUIPPED WITH
 SELF-CLOSING DEVICES.
 7) INTERIOR CORRIDOR WALLS TO BE AT
 LEAST 1/2 HOUR FIRE RATED.
 8) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON THE DRAWINGS. CUT SHEETS, FLOOR
 PLANS AND WIRING DIAGRAM REQUIRED.
 9) A KNOX-BOX WILL BE REQUIRED FOR
 FIRE RESCUE ACCESS.
 10) NO FIRE EXTINGUISHERS SHOWN.
 11) NO OPENINGS ARE ALLOWED WITHIN 10
 FEET OF EXIT STAIRS. IF OPENINGS ARE
 PRESENT, THEY ARE TO BE PROTECTED.