| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESS TO |
| | BE INSTALLED ON BUILDING AND COMPLY WITH |
| | CITY CODE REQUIREMENTS. |
| | 2) DOOR SWING IMPROPER ON MERCANTILE |
| | SPACE THAT DISPLAYS A 77 FOOT MAXIMUM |
| | TRAVEL DISTANCE. THE OCCUPANT LOAD |
| | IS MORE THAN 50, SO EXIT DOORS SHALL |
| | SWING IN THE DIRECTION OF EXIT TRAVEL. |
| | 3) FIRE SPRINKLER SYSTEM, FIRE |
| | RESCUE CONNECTION SHOWN ON SPRINKLER |
| | DRAWINGS TO BE NO MORE THAN 150 FEET |
| | FROM A FIRE HYDRANT. ENTIRE BUILDING TO |
| | BE COMPLETELY FIRE SPRINKLER PROTECTED. |
| | THIS INCLUDES ALL ELECTRICAL, MECHANICAL |
| | AND SERVICE ROOMS. ALSO VERTICAL SHAFTS. |
| | 4) ELEVATION DRAWINGS DO NOT INCLUDE |
| | HEIGHTS. |
| | 5) FUTURE TENANT SPACES TO BE AT LEAST |
| | ONE HOUR FIRE SEPARATED FROM ONE |
| | ANOTHER. |
| | 6) DOORS TO APARTMENTS TO BE AT LEAST |
| | 20 MINUTE FIRE DOORS EQUIPPED WITH |
| | SELF-CLOSING DEVICES. |
| | 7) INTERIOR CORRIDOR WALLS TO BE AT |
| | LEAST 1/2 HOUR FIRE RATED. |
| | 8) PROVIDE COMPLETE FIRE ALARM SYSTEM |
| | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT |
| | SHOWN ON THE DRAWINGS. CUT SHEETS, FLOOR |
| | PLANS AND WIRING DIAGRAM REQUIRED. |
| | 9) A KNOX-BOX WILL BE REQUIRED FOR |
| | FIRE RESCUE ACCESS. |
| | 10) NO FIRE EXTINGUISHERS SHOWN. |
| | 11) NO OPENINGS ARE ALLOWED WITHIN 10 |
| | FEET OF EXIT STAIRS. IF OPENINGS ARE |
| | PRESENT, THEY ARE TO BE PROTECTED. |