Plan Review Notes
Plan Review Notes For Permit 00110504
Permit Number 00110504
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THE ENTIRE
 STRUCTURE IS BEING RE-DONE. THE HEIGHT
 OF ALL DEVICES NEED TO MEET THE REQ`D
 HEIGHTS GIVEN IN CHAPTER 5 OF THE FAIR
 HOUSING ACT,24 CFR 100.205
  
 2)NOTE: PLEASE NOTE PER 210-63 MISSING
 ROOFTOP GFI`S FOR A/C EQUIPMENT.
  
 3)NOTE:PLEASE NOTE THAT PLANS ARE SHOW-
 -ING J-BOXES BEING SWITCHED. MEANS OF
 EGRESS LIGHITNG IS REQUIRED ANDNEEDS
 TO BE SHOWN PER 210-70
  
 4)NOTE: PLEASE SEE E3.1 FOR STORAGE ROOM
 AS PER LOCAL CODE OUTLET SPACING TO MEET
 210-50.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372