| Plan Review Notes For Permit 00110504 |
| Permit Number |
00110504 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE ENTIRE | | | STRUCTURE IS BEING RE-DONE. THE HEIGHT | | | OF ALL DEVICES NEED TO MEET THE REQ`D | | | HEIGHTS GIVEN IN CHAPTER 5 OF THE FAIR | | | HOUSING ACT,24 CFR 100.205 | | | | | | 2)NOTE: PLEASE NOTE PER 210-63 MISSING | | | ROOFTOP GFI`S FOR A/C EQUIPMENT. | | | | | | 3)NOTE:PLEASE NOTE THAT PLANS ARE SHOW- | | | -ING J-BOXES BEING SWITCHED. MEANS OF | | | EGRESS LIGHITNG IS REQUIRED ANDNEEDS | | | TO BE SHOWN PER 210-70 | | | | | | 4)NOTE: PLEASE SEE E3.1 FOR STORAGE ROOM | | | AS PER LOCAL CODE OUTLET SPACING TO MEET | | | 210-50. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|