| Plan Review Notes For Permit 00110398 |
| Permit Number |
00110398 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-25 00:00:00 | FOLLOW UP OF PAUL SCHMITZ REVIEW ON | | | 12/3/2000. | | | | | | 1.COVER SHEET, GOVERNING CODES, CHANGE | | | TO; 94 STANDARD PLUMBING CODE AND 97 | | | STANDARD GAS CODE. | | | | | | 2.OK | | | | | | 3.CHANGE SHT. A-401 FROM HUB DRAIN TO | | | FLOOR SINK. | | | | | | 4.SHT. P1 LOCATION AND SIZE OF GREASE | | | TRAP ( FOUR GREASE TRAPS ON PROPERTY | | | SHOW LOCATION AND SIZE OF G.T. TO BE | | | USED.) | | | | | | 5.OK | | | | | | 6.OK | | | 7.AIR CHAMBERS (ADD NOTE TO P-3 THAT AIR | | | CHAMBERS TO BE READLY ACCESSIBLE AND | | | RECHARGEABLE) | | | | | | 8.97 SGC TABLE 305.4A SHOULD BE USED TO | | | SIZE GAS PIPE. PIPE SIZE TO GRILL | | | SHOULD 3". ADD TOTAL BTU'S 1,913,400. | | | | | | 9.OK | | | | | | 10.P-2 (IN FLOOR GAS LINE) CHANGE NOTE | | | TO READ LIGHT WEIGHT CONCRETE. | | | | | | 11.CHANGE (P-2 "PLUMBING FIXTURE | | | SCHEDULE") WATER HEATER FROM L.P. TO | | | NATERAL. | | | | | | SECOND REVIEW BY; JOHN LEECH | | | 659-8096 EXT 8377 |
|