2001-01-24 00:00:00***************DENIED*******************
 1. PROVIDE DETAILS ON PLATFORM AREA FOR
 AHU -1 SHOWING CONSTRUCTION AND
 CLEARANCE DETAILS. SHOW COMPLIANCE WITH
 1997 SMC 304.2.1 ACCESSIBLILITY FOR
 SERVICE AND 304.4.1 MINIMUM CLEARANCE
 FOR ACCESS AND REMOVAL OF EQUIPMENT.
 MINIMUM SIZES FOR PASSAGEWAYS AND
 PLATFORM DIMENSIONS TO BE SHOWN ON PLAN.
  
 2. NOTE: SEPARATE PERMITS REQUIRED FOR
 HOOD, SUPPRESSION SYSTEM,AND
 COOLER/ FREEZERS
  
 3.SUBMIT TWO COMPLETE SETS OF SIGNED AND
 SEALED DRAWINGS FOR REVIEW AND
 PROCESSING. ONE SET FOR FIELD AND ONE
 SET FOR THE JOB. THIS SUBMITTAL
 INCLUDED TWO OLD REVISIONS AND ONLY ONE
 NEW SET OF REVISIONS.