2001-01-11 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 2) ALL SUNBRELLA AWNINGS TO BE FIRE
 RETARDANT. PLEASE PROVIDE FLAME
 CERTIFICATIONS TO THIS OFFICE UNDER
 SEPARATE COVER WITH LETTER.
 3) NO COMBUSTIBLES PERMITTED IN MAKE-UP
 AIR PLENUM AREA.
 4) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS, CEILINGS AND
 SEATING CONTAINED WITHIN THE SPACE.
 5) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS. ON JANUARY 11,2001, WRITER
 CALLED AND SPOKE TO TERRY MARCUM OF DK
 ARCHITECTS. HE WAS ADVISED THAT FIRE
 ALARM EQUIPMENT WOULD BE REQUIRED IN THE
 SPACE BUT A SEPARATE FIRE ALARM CONTROL
 PANEL WOULD NOT BE NECESSARY. SEPARATE
 PLANS AND PERMITS WOULD BE REQUIRED.
 6) THERE IS AN AREA NEAR BAR 116 THAT
 HAS ONLY ONE STEP AND IT APPEARS THAT
 AN EXIT SIGN DIRECTS PERSONS TO EXIT
 BY USING THE ONE STEP. CHANGES IN
 ELEVATION IN THE MEANS OF EGRESS LESS
 THAN 21 INCHES SHALL BE BY RAMPS. STAIRS
 WHEN USED TO BE A MINIMUM OF THREE AT
 SEVEN INCHES. IT ALSO APPEARS THAT THIS
 AREA IS NOT WIDE ENOUGH TO SUPPORT
 EXITING THROUGH IT. ON JANUARY 18,2001,
 WRITER ALSO SPOKE TO TERRY MARCUM ABOUT
 THIS.
  