| 2001-01-11 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY |
| | THIS OFFICE. |
| | 2) ALL SUNBRELLA AWNINGS TO BE FIRE |
| | RETARDANT. PLEASE PROVIDE FLAME |
| | CERTIFICATIONS TO THIS OFFICE UNDER |
| | SEPARATE COVER WITH LETTER. |
| | 3) NO COMBUSTIBLES PERMITTED IN MAKE-UP |
| | AIR PLENUM AREA. |
| | 4) PLEASE PROVIDE INTERIOR FINISH |
| | INFORMATION FOR WALLS, CEILINGS AND |
| | SEATING CONTAINED WITHIN THE SPACE. |
| | 5) NO FIRE ALARM EQUIPMENT SHOWN ON |
| | DRAWINGS. ON JANUARY 11,2001, WRITER |
| | CALLED AND SPOKE TO TERRY MARCUM OF DK |
| | ARCHITECTS. HE WAS ADVISED THAT FIRE |
| | ALARM EQUIPMENT WOULD BE REQUIRED IN THE |
| | SPACE BUT A SEPARATE FIRE ALARM CONTROL |
| | PANEL WOULD NOT BE NECESSARY. SEPARATE |
| | PLANS AND PERMITS WOULD BE REQUIRED. |
| | 6) THERE IS AN AREA NEAR BAR 116 THAT |
| | HAS ONLY ONE STEP AND IT APPEARS THAT |
| | AN EXIT SIGN DIRECTS PERSONS TO EXIT |
| | BY USING THE ONE STEP. CHANGES IN |
| | ELEVATION IN THE MEANS OF EGRESS LESS |
| | THAN 21 INCHES SHALL BE BY RAMPS. STAIRS |
| | WHEN USED TO BE A MINIMUM OF THREE AT |
| | SEVEN INCHES. IT ALSO APPEARS THAT THIS |
| | AREA IS NOT WIDE ENOUGH TO SUPPORT |
| | EXITING THROUGH IT. ON JANUARY 18,2001, |
| | WRITER ALSO SPOKE TO TERRY MARCUM ABOUT |
| | THIS. |
| | |