Plan Review Notes
Plan Review Notes For Permit 00110398
Permit Number 00110398
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEWDENIED
 GOVERNING CODE:STD PLBG 94,STD GAS 97
 (1) COVER SHT STD. PLBG CODE 94.
 (2) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW & COMMENTS BEFORE PLBG APPR.
 CONTACT /954-958-5520 PLAN REVIEW.
 (3) SHT A-401 SQUARE BUFFET, HUB DRAINS,
 PROHIBITED, SEC 802 ALL INDIRECT TO
 FLOOR SINKS.
 (4) SHT P-1 LOCATION & SIZE OF EXISTING
 GREASE TRAP.
 (5) SHT P-1 DISHWASHER TO SANITARY
 SEWER, LOCAL ORD. # 2938-96
 (6) SHT P-1 BAR #116 HAND SINK, NO DRAIN
 SEC 701.2 ALL INDIRECT WASTE,6" OFF FLR.
 (7) SHT P-3 AIR CHAMBERS TO BE ACCESSIBL
 & RECHARGEABLE,SEC 607.8.3
 (8) SHT P-3 GAS DIAGRAM, SHOW TOT.BTU'S
 TOT.DEVELOPED LENGTH TO FARTHEST POINT.
 GAS PSI & TABEL USED TO SIZE PIPE.
 AUTO SOV TO BE BELOW CEILING WITH A
 UNION DOWN STREAM OF SOV, NFPA-54,5.5.4
 TYPE OF JOINTS WELDED OR SCREWED? 306.4
 SEDEMENT TRAPS ON DROPS,NFPA-54, 5.5.6
 (9) SHT AC-1 GAS WTR.HTR. RM #108 SHOW
 CALCULATIONS FOR COMBUSTION AIR.
 (10)SHT P-1 BURIED BUILDING PIPING,(GAS)
 308.3.2 NOT APPR.& NOT READLY ACCESSIBLE
 END OF COMMENTS