| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEWDENIED |
| | GOVERNING CODE:STD PLBG 94,STD GAS 97 |
| | (1) COVER SHT STD. PLBG CODE 94. |
| | (2) DEPT OF HOTEL BUSINESS REGULATION |
| | PLAN REVIEW & COMMENTS BEFORE PLBG APPR. |
| | CONTACT /954-958-5520 PLAN REVIEW. |
| | (3) SHT A-401 SQUARE BUFFET, HUB DRAINS, |
| | PROHIBITED, SEC 802 ALL INDIRECT TO |
| | FLOOR SINKS. |
| | (4) SHT P-1 LOCATION & SIZE OF EXISTING |
| | GREASE TRAP. |
| | (5) SHT P-1 DISHWASHER TO SANITARY |
| | SEWER, LOCAL ORD. # 2938-96 |
| | (6) SHT P-1 BAR #116 HAND SINK, NO DRAIN |
| | SEC 701.2 ALL INDIRECT WASTE,6" OFF FLR. |
| | (7) SHT P-3 AIR CHAMBERS TO BE ACCESSIBL |
| | & RECHARGEABLE,SEC 607.8.3 |
| | (8) SHT P-3 GAS DIAGRAM, SHOW TOT.BTU'S |
| | TOT.DEVELOPED LENGTH TO FARTHEST POINT. |
| | GAS PSI & TABEL USED TO SIZE PIPE. |
| | AUTO SOV TO BE BELOW CEILING WITH A |
| | UNION DOWN STREAM OF SOV, NFPA-54,5.5.4 |
| | TYPE OF JOINTS WELDED OR SCREWED? 306.4 |
| | SEDEMENT TRAPS ON DROPS,NFPA-54, 5.5.6 |
| | (9) SHT AC-1 GAS WTR.HTR. RM #108 SHOW |
| | CALCULATIONS FOR COMBUSTION AIR. |
| | (10)SHT P-1 BURIED BUILDING PIPING,(GAS) |
| | 308.3.2 NOT APPR.& NOT READLY ACCESSIBLE |
| | END OF COMMENTS |