2001-01-08 00:00:00***************DENIED*******************
  
 1. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
 3. 1997 SMC 610 REQUIRES LOCATION OF ALL
 FIRE DAMPERS ETC. TO BE CLEARLY SHOWN
 ON PLAN ALONG WITH THE INSTALLATION
 DETAILS BY DESIGNER. NO FIRE DAMPERS
 SHOWN ESP. AT SHAFT WALL PENETRATION.
 4. CLEAR UP CONFLICT BETWEEN EQUIPMENT
 SCHEDULE AND REFRIGERANT PIPE SCHEMATIC
 ON AC-3.
 5. SHOW CFM VALUE OF DROP IN FRONT OF
 BEER COOLER.
 6. INDICATE LOCATIONS OF RETURN AIR
 GRILLS INTO CEILING PLENUM.
 7. NOTE: NO COMBUSTIBLES ALLOWED IN
 RETURN AIR PLENUM ABOVE CEILING AREA.
 PER 1997 SMC 609.1.1 (INCLUDING NO PVC)
 8. DUCT SMOKE DETECTOR TO BE TIED TO
 BUILDING FIRE ALARM SYSTEM.
 9. PROVIDE ELEVATION SHOWING HOOD
 EXHAUST DUCT PITCH REQUIRED 1" PER FOOT
 SLOPE BACK TO HOOD.(BOTH HOODS).
 10. REQUIRED ENCLOSURE FOR GREASE
 EXHAUST DUCT TO BE FOR A SINGLE EXHAUST
 DUCT AND FOR NO OTHER PURPOSE PER 1997
 SMC 505.9. PLAN SHOWS OTHER DUCTS AND
 PIPING IN SHAFT. CLEARANCE FROM DUCT TO
 INSIDE OF ENCLOSURE TO BE MIN. 6" PER
 1997 SMC 505.9.1.
 11. ACCESS TO AHU TO BE PROVIDED FOR
 SERVICE AND CLEANING PER 304.3. PROVIDE
 MANUFACTURES REQUIRED CLEARANCE AREA
 TO BE DEDICATED FOR SERVICE AND CLEANING
 12. NOTE: SEPARATE PERMITS ARE REQUIRED
 FOR WALK IN COOLERS/FREEZERS AND HOOD
 SYSTEMS INCLUDED ASSOCIATED DUCT WORK.
 COMPLETE PLANS ARE REQUIRED AT TIME OF
 MECHANICAL PERMIT APPLICATION FOR THESE
 SYSTEMS PRIOR TO ANY WORK BEING DONE ON
 THEM.