| Plan Review Notes For Permit 00110398 |
| Permit Number |
00110398 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER OR HYDRAULIC | | | CALCULATIONS PROVIDED WITH PLANS.THE | | | ENTIRE SPACE IS TO BE COMPLETELY FIRE | | | SPRINKLER PROTECTED. THIS INCLUDES ALL | | | COOLERS, FREEZERS, MECHANICAL AND | | | STORAGE ROOMS. | | | 2) PROVISIONS ARE TO BE MADE FOR THE | | | SEATING OF AT LEAST TWO HANDICAPPED | | | PERSONS. | | | 3) IT APPEARS THAT THE WAITING AND HOST | | | STATION SIT DIRECTLY IN FRONT OF MAIN | | | ENTRY/EXIT DOORS. | | | 4) ANY CHANGES IN ELEVATION LESS THAN | | | 21 INCHES SHALL BE BY RAMPS. STEPS WHEN | | | USED ARE TO EQUAL AT LEAST THREE AT 7 | | | INCHES EACH. | | | 5) PLATFORMS TO COMPLY WITH FIRE AND | | | BUILDING CODE REGULATIONS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|