2001-01-08 00:00:001) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.THE
 ENTIRE SPACE IS TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THIS INCLUDES ALL
 COOLERS, FREEZERS, MECHANICAL AND
 STORAGE ROOMS.
 2) PROVISIONS ARE TO BE MADE FOR THE
 SEATING OF AT LEAST TWO HANDICAPPED
 PERSONS.
 3) IT APPEARS THAT THE WAITING AND HOST
 STATION SIT DIRECTLY IN FRONT OF MAIN
 ENTRY/EXIT DOORS.
 4) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS. STEPS WHEN
 USED ARE TO EQUAL AT LEAST THREE AT 7
 INCHES EACH.
 5) PLATFORMS TO COMPLY WITH FIRE AND
 BUILDING CODE REGULATIONS.
  