1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE; MISSING AIC RATING | | | OF PANELBOARD"K". PLEASE SHOW. | | | | | | 2)NOTE: PLEASE SEE LOADING OF BRANCH | | | BREAKERS. ALL CONTINUOUS LOADS ARE TO BE | | | SHOWN AT 125%. (LIGHTING ETC) PLEASE | | | SEE LOADS SHOWN, IF 125% IS ADDED THEN | | | LOAD EXCEEDS 80% OF BREAKER PER 384-16D | | | PLEASE SHOW ALL CONTINOUS LOADS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|