Plan Review Notes
Plan Review Notes For Permit 00110398
Permit Number 00110398
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE; MISSING AIC RATING
 OF PANELBOARD"K". PLEASE SHOW.
  
 2)NOTE: PLEASE SEE LOADING OF BRANCH
 BREAKERS. ALL CONTINUOUS LOADS ARE TO BE
 SHOWN AT 125%. (LIGHTING ETC) PLEASE
 SEE LOADS SHOWN, IF 125% IS ADDED THEN
 LOAD EXCEEDS 80% OF BREAKER PER 384-16D
 PLEASE SHOW ALL CONTINOUS LOADS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372