| Plan Review Notes For Permit 00110376 |
| Permit Number |
00110376 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS IN HALLWAYS ARE TO | | | BE INSTALLED AT LEAST THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT BUILDING. | | | 3) FIRE ALARM SYSTEM AND FIRE SPRINKLER | | | SYSTEM TO BE MONITORED BY A LICENSED | | | UL LISTED CENTRAL STATION. | | | 4) ENTIRE SYSTEM TO BE TESTED WITH THE | | | FIRE RESCUE DEPARTMENT. | | | 5) SYSTEM TO BE INSTALLED IN ACCORDANCE | | | WITH NFPA 72. | | | 6) THE SINGLE STATION SMOKE DETECTORS | | | INSTALLED WITHIN THE APARTMENTS ARE TO | | | BE AUDIBLE WITHIN THE SLEEPING ROOMS OF | | | THAT UNIT. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|