2002-01-14 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT THE BURIAL
 DEPTH FOR SERVICE ENTRANCE CONDUCTORS
 ARE SHOWN AT TWO DIFFERENT DEPTHS ON
 FRONT PAGE ETC-0.? PLEASE SEE 300-5
 FOR MIN 24" DEPTH.
  
 2)NOTE: PLEASE SEE ETC-5, PLEASE CLARIFY
 SIZING OF EQUIPMENT/ AIC RATINGS ETC
 ON LINE DIAGRAM SHOWN ON ETC-5, PLEASE
 NOTE NO DETAILS WERE GIVEN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  