Plan Review Notes
Plan Review Notes For Permit 00110364
Permit Number 00110364
Review Stop P
Sequence Number 2
Notes
Date Text
2001-04-08 00:00:00PLUMBING PLAN REVIEWDENIED
 CODE REFERENCE SPC 94
 (1)SHT PTC-02 CONTACT DEPT OF HOTEL BUS-
 INESS REGULATION, PLAN REVIEW,FOR THIER
 COMMENTS, BEFORE PLBGREVIEW APPROVAL.
 954-958-5520,3 SETS OF PLANS.
 (2)SHT PTC-02 GREASE WASTE: COMPLY WITH
 SEC 921 COMBINATION WASTE & VENT SYSTEM
 EVERY PIPE SHALL BE 2 PIPE SIZES LARGER
 THAN REQUIRED,MAIN LINE 4", BRANCHES3",
 MINIMUM VENT SIZE 2",UPSTREAM,DOWNSTREAM
 (3)SHT PTC-02 SEC 804.1, ALL INDIRECT
 WASTE TO FLOOR SINKS,6" OFF FLOOR.
 (4)SHT PTC-02 SEE ATTACHED GAS PERMIT
 APPLICATION REQUIRMENTS,.
 (5)SHT LP-02 PUBLIC REST RM. FACILITIES,
 TAB 407,SHOW CALCULATIONS FOR NUMBER OF
 FIXTURES REQUIRED.
 (6) SHT PTC-01 SHOW SEATING DIAGRAM FOR
 NUMBER OF PERSONS,NUMBER OF MEALS SERVED
 (7)SHT PTC-01 CONTACT WPB REGIONAL SEWER
 TREATMENT PLANT,RODNEY COMPO,837-4074
 FOR GREASE TRAP SIZE, AND STANDARDS.
 (8) SHT PTC -02 BACK FLOW PREVENTER
 REQUIRED ON DOMESTIC WATER SERVICE,
 SPC-94 SEC 601.6
 END OF COMMENTS, PAULSCHMITZ
 QUESTIONS561-659-8096 X 8233