| Date |
Text |
| 2001-04-08 00:00:00 | PLUMBING PLAN REVIEWDENIED |
| | CODE REFERENCE SPC 94 |
| | (1)SHT PTC-02 CONTACT DEPT OF HOTEL BUS- |
| | INESS REGULATION, PLAN REVIEW,FOR THIER |
| | COMMENTS, BEFORE PLBGREVIEW APPROVAL. |
| | 954-958-5520,3 SETS OF PLANS. |
| | (2)SHT PTC-02 GREASE WASTE: COMPLY WITH |
| | SEC 921 COMBINATION WASTE & VENT SYSTEM |
| | EVERY PIPE SHALL BE 2 PIPE SIZES LARGER |
| | THAN REQUIRED,MAIN LINE 4", BRANCHES3", |
| | MINIMUM VENT SIZE 2",UPSTREAM,DOWNSTREAM |
| | (3)SHT PTC-02 SEC 804.1, ALL INDIRECT |
| | WASTE TO FLOOR SINKS,6" OFF FLOOR. |
| | (4)SHT PTC-02 SEE ATTACHED GAS PERMIT |
| | APPLICATION REQUIRMENTS,. |
| | (5)SHT LP-02 PUBLIC REST RM. FACILITIES, |
| | TAB 407,SHOW CALCULATIONS FOR NUMBER OF |
| | FIXTURES REQUIRED. |
| | (6) SHT PTC-01 SHOW SEATING DIAGRAM FOR |
| | NUMBER OF PERSONS,NUMBER OF MEALS SERVED |
| | (7)SHT PTC-01 CONTACT WPB REGIONAL SEWER |
| | TREATMENT PLANT,RODNEY COMPO,837-4074 |
| | FOR GREASE TRAP SIZE, AND STANDARDS. |
| | (8) SHT PTC -02 BACK FLOW PREVENTER |
| | REQUIRED ON DOMESTIC WATER SERVICE, |
| | SPC-94 SEC 601.6 |
| | END OF COMMENTS, PAULSCHMITZ |
| | QUESTIONS561-659-8096 X 8233 |