Plan Review Notes
Plan Review Notes For Permit 00110364
Permit Number 00110364
Review Stop M
Sequence Number 2
Notes
Date Text
2001-04-03 00:00:00******************PROVISO***************
  
  
 1.EXHAUST DUCT SHALL BE A MINIMUM OF
 10' ADJACENT OF THE FRESH AIR
 INTAKE.
  
 2.A MINIMUM OF 18" IS REQURIED
 BETWEEN ROOF SURFACE AND TO
 BOTTOM OF SUPPORT TO THE CONDENSER
 UNIT STAND AS PER THE AMMENDED 1997
 SMC 304.2.5.
  
 3.ADDITIONAL PLANS & PERMIT REQUIRED
 FOR HOOD, GREASE AND SUPPLY DUCT.
  
 4.ADDITIONAL PLANS & PERMIT REQUIRED
 FOR THE FIRE SUPPRESSION SYSTEM.