2001-01-08 00:00:00*********DENIED*************************
  
 1.PROVIDE INFORMATION ON ACCESS AND
 SERVICE TO AHU ABOVE BATHROOMS SHOWING
 COMPLIANCE WITH 1997 SMC 304.2.
 2.WORK ROOM WITH 400 CFM OF SUPPLY AIR
 NEEDS PATH FOR RETURN AIR BACK TO AHU.
 PER 1997 SMC 501.2